Specifications

Test Operation SiBE341027
62 Test Operation
* How to calculate additional refrigerant charging amount (Unit: 0.1 kg)
+ B (Correction with outdoor unit capacity) + C (Correction with indoor unit capacity)
Model A B kg
C kg
100% >100%
RQYQ
8PY1B
1.00
-6.8kg
0.0kg 0.0kg
10PY1B -7.9kg
12PY1B -9.3kg
14·16PY1B -14.1kg
R
Total length of
φ22.2-mm
liquid pipe)
× 0.37
Total length of
φ9.5-mm
liquid pipe)
× 0.059
Total length of
φ6.4-mm
liquid pipe)
× 0.022 × A
Total length of
φ19.1-mm
liquid pipe)
× 0.26
Total length of
φ12.7-mm
liquid pipe)
× 0.12
Total length of
φ15.9-mm
liquid pipe)
× 0.18
++
+
++