Specifications

Detailed Control Functions SiBE341027
56 Function
2.5.5 STD Compressor Overload Protection
This control is used to prevent abnormal heating due to overcurrent to the compressor resulting from failures
of STD compressor such as locking.
STD compressor ON
CT detection current value>28.8ADemand to operate.
STD compressor OFF for 30 min.
(2 times per 90 minutes at max.)
Stop due to error
("
E6" displayed)