Specifications

SiBE341027 Detailed Control Functions
Function 55
2.5.4 Inverter Protection Control
Inverter current protection control and inverter fin temperature control are performed to prevent tripping due to
an error, or transient inverter overcurrent, and fin temperature increase.
[Inverter overcurrent protection control]
In the case of multi-outdoor-unit system, each INV. compressor performs these controls in the following sequence.
[Inverter fin temperature control]
In the case of multi-outdoor-unit system, each INV. compressor performs these controls in the following sequence.
INV. Comp.: 1 step down INV. Comp.: 1 step up
• INV. current value > 26.5 A
• After 15 sec.
&
INV. current value > 27.6A continues for
260 seconds.
Restart standby
(3 times per 60 min. at max.)
4 times per 60 min.
INV. current value < 26.5 A
continues for 20 sec.
Stop due to error
("
L8" displayed)
Normal operation
• Inverter current value < 26.5 A
• INV. upper limit frequency = max (210 Hz)
&
Inverter current value
>26.5A
INV. Comp.: 1 step down INV. Comp.: 1 step up
Tfin > 84˚C
• After 15 sec.
&
Tfin > 98˚C
Restart standby
(3 times per 60 min. at max.)
4 times per 60 min.
Normal operation
Tfin > 84˚C
Tfin < 81˚C
• INV upper limit frequency = max (210 Hz)
&
Tfin < 81˚C
continues for 3 min.
(Without preconditions)
(Without preconditions)
Current step maintenance
Stop due to error
("
L4" displayed)