Specifications

SiBE341027 Features
General Information 15
For the existing piping, please check the followings
The existing piping should meet the condition of design pressure 3.3MPa.
Concretely, it should meet the minimum thickness for VRVIII-Q shown in the table below.
Existing Daikin R-22 piping meets the minimum thickness of VRVIII-Q.
The existing piping should not be corroded on the external appearance.
Taper grade (O type, 1/2H type) in the table indicate the material types specified in JIS H3300.
In case of bending O material, set the round bending to 3xD or more (D: Outer Diameter)
1/2H materials are calculated without setting the bending.
Outer diameter of piping
VRVIII-Q Daikin for R-22 (for reference)
Material
Minimum thickness
(mm)
Material
Minimum thickness
(mm)
φ
6.4
{
0.4
{
0.80
φ
9.5
{
0.5
{
0.80
φ
12.7
{
0.7
{
0.80
φ
15.9
{
0.9
{
0.99
φ
19.1 1/2H 0.6
{
0.80
φ
22.2 1/2H 0.6 1/2H 0.80
φ
25.4 1/2H 0.7 1/2H 0.88
φ
28.6 1/2H 0.8 1/2H 0.99
φ
31.8 1/2H 0.9 1/2H 1.10
φ
34.9 1/2H 1.0 1/2H 1.21
φ
38.1 1/2H 1.1 1/2H 1.32
φ