Specifications
Troubleshooting by Remote Controller SiBE341027
160 Service Diagnosis
2.35 Transmission Error (Across Outdoor Units)
Remote
Controller
Display
U7
Applicable
Models
RQYQ-PY1B
Method of Error
Detection
Micro-computer checks if transmission between outdoor units is normal.
Error Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Connection error in connecting wires between outdoor unit and external control adaptor for
outdoor unit
Connection error in connecting wires across outdoor units
Setting error in switching cool/heat
Unified address setting error for cool/heat
(external control adaptor for outdoor unit)
Defective outdoor unit PCB (A1P)
Defective external control adaptor for outdoor unit