Specifications
Troubleshooting by Remote Controller SiBE341027
156 Service Diagnosis
2.33 Transmission Error (between Indoor and Outdoor Units)
Remote
Controller
Display
U4
Applicable
Models
All indoor unit models
RQYQ-PY1B
Method of Error
Detection
The error is generated when the micro-computer detects that the transmission between the
indoor and outdoor unit is not normal.
Error Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
or wrong wiring
Outdoor unit power supply is OFF
System address does not match
Defective outdoor unit main PCB (A1P)
Defective indoor unit PCB