Specifications

SiBE341027 Troubleshooting by Remote Controller
Service Diagnosis 149
2.29 Refrigerant Shortage
Remote
Controller
Display
U0
Applicable
Models
RQYQ-PY1B
Method of Error
Detection
Detect refrigerant shortage based on the temperature difference between low pressure or
suction pipe and heat exchanger.
Error Decision
Conditions
[In cooling mode]
Low pressure becomes 0.1MPa or less.
[In heating mode]
The degree of superheat of suction gas becomes 20 degrees or more.
SH= Ts1 –Te
Ts1: Temperature detected by suction pipe thermistor
Te : Low pressure equivalent saturation temperature
Error is not determined. The unit continues operation.
Supposed
Causes
Refrigerant shortage or refrigerant clogging (wrong piping)
Defective thermistor (R8T, R9T)
Defective low pressure sensor
Defective outdoor unit PCB (A1P)