Specifications

SiBE341027 Troubleshooting by Remote Controller
Service Diagnosis 143
2.25 Transmission System Error (between Inverter and Main
PCB)
Remote
Controller
Display
LC
Applicable
Models
RQYQ-PY1B
Method of Error
Detection
Check the communication state between inverter PCB and main PCB by micro-computer.
Error Decision
Conditions
When the transmission is not carried out in a specified period of time or longer.
Supposed
Causes
Incorrect transmission wiring between the inverter PCB and outdoor unit main PCB
Defective outdoor unit main PCB (transmission section)
Defective inverter PCB
Defective noise filter
External factor (noise etc.)
Defective inverter compressor
Defective fan motor