Service manual

Si06-305 Main Functions
Function and Control 17
1.3 Air Flow Selection
When setting the
air flow selection
switch to .
Air conditioner automatically decides the appropriate blowing pattern depending on the
operating mode / situation.
During Dry mode, so that cold air does not come into direct contact with people, air is blown
upper air outlet.
When setting the
air outlet
selection switch
to .
Regardless of the operating mode or situation, air blows from the upper air outlet.
Use this switch when you do not want air coming out of the lower air outlet. (While sleeping
etc..)
Operating mode Situation Blowing pattern
Cool mode
When the room has become
fully cool, or when one hour has
passed since turning on the air
conditioner.
So that air does not come into direct contact
with people, air is blown upper air outlet,
room temperature is equalised.
At start of operation or other
times when the room is not fully
cooled.
Air is blown
from the upper
and lower air
outlets for high
speed cooling
during Cool
mode, and for
filling the room
with warm air
during Heat
mode.
Heat mode
At times other than below.
(Normal time.)
At start or when air temperature
is low.
So that air does not come into direct contact
with people. Air is blown upper air outlet.