00_CV_3P253189-4E.
01_EN_3P253189-4E.fm Page 1 Monday, September 6, 2010 4:20 PM Safety Precautions • Read these Safety Precautions carefully to ensure correct installation. • This manual classifies the precautions into DANGER, WARNING and CAUTION. Be sure to follow all the precautions below: they are all important for ensuring safety. DANGER ............... Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING .............
01_EN_3P253189-4E.fm Page 2 Monday, September 6, 2010 4:20 PM Safety Precautions WARNING • After connecting all wiring be sure to shape the cables so that they do not put undue stress on the electrical covers, panels or terminals. Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, fire or equipment damage.
01_EN_3P253189-4E.fm Page 3 Monday, September 6, 2010 4:20 PM Accessories Accessories supplied with the outdoor unit: (B) Drain plug (Heat pump models) (A) Installation manual 1 1 There is on the bottom packing case. Precautions for Selecting the Location 1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
01_EN_3P253189-4E.fm Page 4 Monday, September 6, 2010 4:20 PM Outdoor Unit Installation Drawings Wrap the insulation pipe with the finishing tape from bottom to top. Max. allowable length 49.2ft (15m) * Min. allowable length 4.92ft (1.5m) Max. allowable height 39.3ft (12m) Additional refrigerant required for refrigerant pipe exceeding 33ft (10m) in length. 0.22oz/ft Gas pipe O.D. 3/8 inch (9.5mm) Liquid pipe O.D. 1/4 inch (6.4mm) * Be sure to add the proper amount of additional refrigerant.
01_EN_3P253189-4E.fm Page 5 Monday, September 6, 2010 4:20 PM Installation Guidelines • Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines below. • For any of the below installation patterns, the wall height on the exhaust side should be 47-1/4 inch (1200mm) or less.
01_EN_3P253189-4E.fm Page 6 Monday, September 6, 2010 4:20 PM Outdoor Unit Installation 3. Flaring the pipe end 1) Cut the pipe end with a pipe cutter. 2) Remove burrs with the cut surface facing downward so that the chips do not enter the pipe. 3) Put the flare nut on the pipe. 4) Flare the pipe. 5) Check that the flaring is properly made. (Cut exactly at right angles.) Remove burrs. Flaring Set exactly at the position shown below.
01_EN_3P253189-4E.fm Page 7 Monday, September 6, 2010 4:20 PM 5. Purging air and checking gas leakage • When piping work is completed, it is necessary to purge the air and check for gas leakage. WARNING • Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle. • When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
01_EN_3P253189-4E.fm Page 8 Monday, September 6, 2010 4:20 PM Outdoor Unit Installation 6. Refilling the refrigerant Check the type of refrigerant to be used on the machine nameplate. Precautions when adding R410A Fill from the liquid pipe in liquid form. It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation. 1) Before filling, check whether the cylinder has a siphon attached or not.
01_EN_3P253189-4E.fm Page 9 Monday, September 6, 2010 4:20 PM Pump Down Operation In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 1) 2) 3) 4) Remove the valve cap from liquid stop valve and gas stop valve. Carry out forced cooling operation. After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench. After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.
01_EN_3P253189-4E.fm Page 10 Monday, September 6, 2010 4:20 PM Wiring WARNING • Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire. • Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal block.) Doing so may cause electric shock or fire. • Be sure to install a ground fault circuit interrupter breaker.
01_EN_3P253189-4E.fm Page 11 Monday, September 6, 2010 4:20 PM CAUTION • When connecting the connection wires to the terminal board using a single core wire, be sure to perform curling. Problems with the work may cause heat and fires. Strip wire end to this point. Good Excessive strip length may cause electrical shock or leakage. Wrong Stripping wire at terminal block 3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.
01_EN_3P253189-4E.fm Page 12 Monday, September 6, 2010 4:20 PM Trial Operation and Testing 1. Trial operation and testing 1-1 Measure the supply voltage and make sure that it falls in the specified range. 1-2 Trial operation should be carried out in either cooling or heating mode. ■ For heat pump • In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable temperature. 1) Trial operation may be disabled in either mode depending on the room temperature.
00_CV_3P253189-4E.fm Page 2 Monday, September 6, 2010 4:18 PM Two-dimensional bar code is a code for manufacturing.