Specifications

SiUS39-601 Special Control
Function 45
3.5 Restart Standby
Actuator Operation
Compressor OFF
Outdoor unit fan
Ta>86°F: STEP5
Ta86°F: OFF
Four way valve Holds
Main motorized valve (EV1) 0 pls
Subcooling motorized valve (EV2) 0 pls
Hot gas bypass valve (SVP) OFF
Oil equalization valve (SVO) ON
Receiver gas charging valve (SVL) OFF
Receiver gas discharging valve (SVG) OFF
Non-operating unit gas discharging valve (SVSG) OFF
Non-operating unit liquid pipe stop valve (SVSL) ON
Ending conditions 5 min.