Specifications
Specifications SiUS39-601
18 Specifications
Ceiling Suspended Type
Notes:
★
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25ft (Horizontal)
★
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
★
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model FXHQ12MVJU FXHQ24MVJU FXHQ36MVJU
★1 Cooling Capacity Btu/h 12,000 24,000 36,000
★2 Heating Capacity Btu/h 13,500 27,000 40,000
Casing / Color White(10Y9/0.5) White(10Y9/0.5) White(10Y9/0.5)
Dimensions: (H×W×D) in 7-11/16
×
37-13/16
×
26-3/4 7-11/16
×
55-1/8
×
26-3/4 7-11/16
×
62-5/8
×
26-3/4
Coil (Cross
Fin Coil)
Rows × Stages × FPI 2×12×15 3×12×15 2×12×15+2×10×15
Face Area ft² 1.96 3.15 3.66+2.95
Fan
Model 3D12K1AA1 3D12K2AA1 —
Type Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output W 62 130 130
Air Flow Rate (H/L) cfm 410/340 710/600 830/670
Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for Cooling
and Heating
Microprocessor Thermostat for Cooling
and Heating
Microprocessor Thermostat for Cooling
and Heating
Sound Absorbing Thermal Insulation Material Glass Wool Glass Wool Glass Wool
Air Filter Resin Net (with Mold Resistant)
Piping
Connections
Liquid Pipes in
φ
1/4 (Flare Connection)
φ
3/8 (Flare Connection)
φ
3/8 (Flare Connection)
Gas Pipes in
φ
1/2 (Flare Connection)
φ
5/8 (Flare Connection)
φ
5/8 (Flare Connection)
Drain Pipes in
VP20
External Dia. 1
Internal Dia. 3/4
VP20
External Dia. 1
Internal Dia. 3/4
VP20
External Dia. 1
Internal Dia. 3/4
Machine Weight (Mass) Lbs 55 80 90
★
4 Sound Level (H/L) dBA 42 44 46
Safety Devices
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Connectable Outdoor Unit R-410A Series R-410A Series R-410A Series
Standard Accessories
Operation Manual, Installation Manual,
Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation for
Fitting, Clamps, Washers.
Operation Manual, Installation Manual,
Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation for
Fitting, Clamps, Washers.
Operation Manual, Installation Manual,
Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation for
Fitting, Clamps, Washers.
Drawing No. C:4D049326
() () ()