Specifications
SPECIFICATIONS
FXMQ-MF
125, 200, 250
FXMQ200-250MF
ACCESSORIES
SPECIFICATIONS
Outdoor air processing unit, ventilation
and air processing
OTHERS FXMQ125MF FXMQ200-250MF
High eciency lter
-65%
KAFJ372L140
-90%
KAFJ373L140
Replacement long life lter
KAFJ371L140 KAFJ371L280
Filter chamber
1
KDJ370SL140 KDJ370SL280
Drain pump kit
KDU30LL250VE
Adapter for wiring
KRP1B61
VENTILATION FXMQ125MF FXMQ200MF FXMQ250MF
Capacity
cooling kW
14.0 22.4 28.00
heating kW
8.9 13.9 17.40
Power input
cooling kW
0.359 0.548 0.638
heating kW 0.359 0.548 0.638
Casing material Galvanised steel
Dimensions
unit
height x width x depth
mm 470x744x1,100 470x1,380x1,100
Weight
unit kg 86 123
Heat exchanger
rows quantity 3
stages quantity 26
n pitch mm 2.0
face area m 0.28 0.65
Fan
type Sirocco fan
air ow rate - 50hz heat exchange mode/bypass mode
18.0 - 28.0 - 35.0
Fan motor model D13/4G2DA1
Refrigerant
type R-410A
Refrigerant control Electronic expansion valve
Piping
connections
liquid type/OD mm Flare connection/9.52
gas type/OD mm Flare connection/15.9 Braze connection/19.1 Braze connection/22.2
drain
PS1B
Power supply phase/frequency/voltage Hz/V
1~/50/220-240
(1) Cooling: outdoor temp.: 33°CDB, 28°CWB (68%RH), discharge set temperature: 18°CDB, equivalent piping length 7.5m (horizontal) (2) Heating: outdoor temp. 0°CDB, -2.9°CWB (50%RH); discharge set temp. 25°CDB; equivalent piping length: 7.5m
(horizontal) (3) Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (4) The air lter is not a standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric method
(gravity method) 50% or more. (5) When connected to VRV water-cooled outdoor units a mix of ventilation units and VRV indoor units is not possible
OTHERS FXMQ-MF
Wiring adapter for electrical appendices
(control and monitoring F1 F2)
KRP2A61
Wiring adapter for electrical appendices
(control and monitoring P1 P2)
KRP4A51
INDIVIDUAL CONTROL SYSTEMS FXMQ-MF
Wired remote control BRC1E52A / BRC1D52
CENTRALISED CONTROL SYSTEMS FXMQ-MF
Centralised remote control DCS302C51
Unied ON/OFF control DCS301B51
Schedule timer DST301B51
Notes
(1) Filter chamber has a suction-type ange. (Main unit does not).
Some options may not be usable due to the equipment installations conditions. Please conrrm prior to ordering.
Some options may not be used in combination.
Operating sound may increase somewhat depending on the options used.
21