User`s manual
INDOOR UNIT LINEUP
2019
Slim Ceiling Mounted
Duct Type
Slim design, quietness and
static pressure switching
External static pressure selectable by remote
controller switching make this indoor unit a very
comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models.
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.
Only 200 mm in height, this model can be
installed in rooms with as little as 240 mm depth
between the drop-ceiling and ceiling slab.
Only 700 mm in width and 23 kg in weight, this
model is suitable to install in limited spaces like
drop-ceilings in hotels.
1,100 mm in width for the FXDQ63NB model.
200 mm
900 mm
Suction grille*
AIR
AIR
Discharge grille*
Air filter
Suspension bolt*
240 mm
* To be obtained locally
Only 700 mm
200 mm
Great for
hotel use!
Suited for use in drop-ceilings!
Drain pump is equipped as standard accessory
with 750 mm lift.
Ceiling Mounted
Built-in Type
Highly flexible for various application
750 mm
Ceiling
FXDQ20PB/FXDQ25PB/FXDQ32PB
FXDQ40NB/FXDQ50NB/FXDQ63NB
Low operation sound level
(dB(A))
The values of operation sound level represent those for rear-suction operation.
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.
Control of the airflow rate has been improved
from 2-step to 3-step control.
36/34/32
63
35/33/31
50
34/32/30
40
33/31/29
20/25/32
Sound level
(HH/H/L)
FXDQ-PB/NB
250 mm
Min.
350 mm
Highly flexible installation is possible
with a complete lineup of optional
kits to satisfy various needs, such as
the design concept, interior
decoration and so on.
The unit can be installed, if there is
a space of 350 mm above ceiling.
(when suction panel is used.)
Drain pump is equipped as standard
accessory with 250 mm lift.
High external static pressure allows the use of
flexible ducts of various length.
Low operation sound level
41/33.5
Sound level
(H/L)
20/25/32
40 50 63 80/100 125
41/34.5 43/37 45/38.5 48/43 49/41.5
(230 V)(dB(A))
FXSYQ-M
Standard
With duct
Cassette style
(standard filter)
Cassette style (high efficiency filter)
Long-life filter
Long-life filter
Air suction
canvas bellows
Air suction panel
Air suction panel
Access panel
Access panel
Air suction
canvas bellows
Ceiling return
Long-life filter
Screening
door
High efficiency
filter
Installation examples ( Optional parts)
The values of operation sound level are based on Australian Standard 1217.6-1985.
Measurement is based on bottom-return air entry.
FXSYQ20M/FXSYQ25M/FXSYQ32M
FXSYQ40M/FXSYQ50M/FXSYQ63M
FXSYQ80M/FXSYQ100M/FXSYQ125M
New