Specifications

Specifications EDUS391000-F12
2 FXTQ-PA
1. Specifications
Air Handling Unit
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB(27°CDB), 67°FWB(19.4°CWB)
Outdoor temperature: 95°FDB (35°C)
Equivalent ref. piping: 25ft (7.5 m) (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB (21°C)
Outdoor temperature: 47°FDB (8.3°CDB) , 43°FWB (6.1°CWB)
Equivalent ref. piping: 25ft (7.5 m) (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Air filter is not standard accessory, but please mount it in the duct system of the suction side.
5 A field-supplied secondary drain pan may be required.
Model FXTQ12PAVJU
FXTQ18PAVJU FXTQ24PAVJU FXTQ30PAVJU
Power Supply 1 phase, 208/230V, 60Hz
1, 3 Cooling capacity Btu/h 12,000
18,000 24,000 30,000
2, 3 Heating capacity Btu/h 13,500
20,000 27,000 34,000
Dimensions: (H×W×D) in (mm) 46-3/4 × 19-1/2 × 22 (1187 x 495 x 559)
53-1/4 × 22 × 24
(1353 x 559 x 609)
Coil
Type Cross fin coil
Rows×Stages×FPI 6 × 14 × 15 4 × 22 × 15
Face area ft² (m²) 3.30 (1) 6.02 (1.8)
Fan
Model ECM (1/2HP)
ECM (3/4HP)
Type Sirocco fan
Motor output HP 1/2
3/4
Airflow rate (H/L) CFM 400/280 600/420 800/560 1,000/700
External static
pressure
“Wg Up to 0.5
Drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Air filter 4
Weight lbs (kg) 121 (55) 149 (67.6)
Piping connections
Liquid in (mm) 1/4 (6.4) (Brazed) 3/8 (9.5) (Brazed)
Gas in (mm) 1/2 (12.7) (Brazed) 5/8 (15.8) (Brazed)
Drain in (mm) 3/4 (19.1) 5
Safety devices
Fuse,
Fan driver overload protector
Refrigerant control Electronic expansion valve
Connectable outdoor unit R-410A VRV Series
Standard accessories Operation manual, Installation manual
Drawing No. C: 3D068193
1 and 2 are the performance for vertical installation.
For horizontal installation, capacity could decrease by about 10%.