Specifications
EDUS391000-F12 Installation
FXTQ-PA 17
3P250363-2B
English 4
Where piping between indoor and outdoor units is •
possible within the allowable limit. (Refer to the installa-
tion manual for the outdoor unit.)
If a return-air duct is not installed, carefully select the •
place and method of product installation so that air fl ow
into the product will not be blocked.
If installed vertically
24 or more
(length : in.)
(Top view)
H
(Front view)
Fig. 1-1
Air outlet
Air inlet
If installed horizontally
H
(Front view)
Air outlet
Air inlet
24 or
more
(Side view)
H
Fig. 1-2
WARNING
When installing the unit horizontally, be sure to tilt the unit in •
the direction shown in Fig. 1-2. If the unit is tilted in any other
way, water can leak.
Ensure suffi cient space for the bottom of the product
•
(H dimensions) so that a downward slope of 1/100 can
be maintained for drain piping, as described for the intake
duct installation and in “6. DRAIN PIPING WORK”.
[ PRECAUTION ]
Install the indoor and outdoor units, power supply wiring •
and connecting wires at least 3.5 ft. away from televi-
sions or radios in order to prevent image interference or
noise. (Depending on the radio waves, a distance of 3.3
ft. may not be suffi cient to eliminate the noise.)
If installing the wireless kit in a room with electronic •
fl uorescent lighting (inverter or rapid start type), the
remote controller’s transmission distance may be short-
ened. Indoor units should be installed as far away from
fl uorescent lighting as possible.
DANGER
Do not install unit in an area where fl ammable materials are •
present due to the risk of an explosion resulting in serious
injury or death.
WARNING
If the supporting structural members are not strong enough •
to take the unit’s weight, the unit could fall out of place and
cause serious injury.
PREPARATIONS BEFORE INSTALLA-4.
TION AND INSTALLATION
When installing the product, refer to “3. SELECTING (1)
INSTALLATION SITE” and consider the product size
as shown Fig. 2 and Table 1.
C
D
11E
B
A
F
G
1-1/8
Gas line
Fig. 2
H1-3/16
(1-3/16)
1
3-1/4
I2-7/8
(1-3/16)
Liquid line
(length: in.)