EDUS391000 - F12 FXTQ-PA Air Handling Unit AMERICAS
EDUS391000-F12 FXTQ-PA Air Handling Unit 1. 2. 3. 4. 5. Specifications ..............................................................................................2 Dimensions .................................................................................................4 Piping Diagrams..........................................................................................6 Wiring Diagrams..........................................................................................
Specifications EDUS391000-F12 1. Specifications Air Handling Unit Model FXTQ12PAVJU FXTQ18PAVJU Power Supply FXTQ24PAVJU 1, 3 Cooling capacity Btu/h 12,000 18,000 24,000 2, 3 Heating capacity Btu/h 13,500 20,000 27,000 Dimensions: (H×W×D) in (mm) 6 × 14 × 15 ft² (m²) Model 4 × 22 × 15 3.30 (1) 6.02 (1.
EDUS391000-F12 Specifications Air Handling Unit Model FXTQ36PAVJU Power Supply FXTQ42PAVJU FXTQ48PAVJU FXTQ54PAVJU 1 phase, 208/230V, 60Hz 1, 3 Cooling capacity Btu/h 36,000 42,000 48,000 54,000 2, 3 Heating capacity Btu/h 40,000 47,000 54,000 60,000 Dimensions: (H×W×D) in (mm) 53-1/4 × 22 × 24 (1353 x 559 x 610) Type Coil Cross fin coil Rows×Stages×FPI Face area 4 × 22 × 15 8 × 22 × 15 ft² (m²) 6.02 (1.
Dimensions EDUS391000-F12 2.
EDUS391000-F12 Dimensions 3D068377A FXTQ24PAVJU FXTQ30PAVJU FXTQ36PAVJU FXTQ42PAVJU FXTQ48PAVJU FXTQ54PAVJU FXTQ-PA 5
Piping Diagrams EDUS391000-F12 3.
EDUS391000-F12 Wiring Diagrams 4. Wiring Diagrams FXTQ12PAVJU / FXTQ18PAVJU / FXTQ24PAVJU / FXTQ30PAVJU / FXTQ36PAVJU / FXTQ42PAVJU / FXTQ48PAVJU / FXTQ54PAVJU PROTECTIVE GROUND NOISELESS GROUND 3D065036F NOTE: This unit is not equipped with a return air sensor. A remote sensor is required when not using a BRC1E71 Controller or if this controller is not positioned to sense space temperature.
Electric Characteristics EDUS391000-F12 5. Electric Characteristics 5.1 Indoor Unit Symbols: MCA MOP IFM HP FLA : : : : : Minimum Circuit Amps (A) Maximum Overcurrent Protective Device (A) Indoor Fan Motor Fan Motor Rater Output (HP) Full Load Amps (A) NOTE: 1. Voltage range: Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. 2. Maximum allowable voltage imbalance between phases is 2%. 3.
EDUS391000-F12 5.
Capacity Tables EDUS391000-F12 6. Capacity Tables 6.1 Cooling Capacity FXTQ-PA Outdoor Unit size air temp. 12 18 24 30 36 42 48 54 TC: SHC: 10 °FDB 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 [Cooling capacity] 61.0 °FWB TC SHC MBh MBh 9.5 7.0 9.5 7.0 9.5 7.0 9.5 7.0 9.5 7.0 9.5 7.0 9.5 7.0 9.5 7.0 14.2 11.3 14.2 11.3 14.2 11.3 14.2 11.
EDUS391000-F12 6.2 Capacity Tables Heating Capacity FXTQ-PA Unit size 12 18 24 30 36 42 48 [Heating capacity] Outdoor air temp. °FDB 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.
Airflow Auto Adjustment Characteristics EDUS391000-F12 7. Airflow Auto Adjustment Characteristics FXTQ12PAVJU FXTQ18PAVJU 3D068210 3D068211 Notes: 1. If the airflow is less than 10% of the rated air volume, it is automatically adjusted to the rated volume. 2. The unit automatically adjusts external static pressure between 0.0 in.W.C. - 0.5 in.W.C (When fan speed is "H"). 3. Airflow cannot operate at the rated value if it is outside the ESP range in the above graph. 4.
EDUS391000-F12 Airflow Auto Adjustment Characteristics FXTQ24PAVJU FXTQ30PAVJU 3D068212 FXTQ42PAVJU FXTQ36PAVJU 3D068213 FXTQ48PAVJU 3D068215 3D068214 FXTQ54PAVJU 3D068216 3D068217 Notes: 1. If the airflow is less than 10% of the rated air volume, it is automatically adjusted to the rated volume. 2. The unit automatically adjusts external static pressure between 0.0 in.W.C. - 0.5 in.W.C (When fan speed is "H"). 3.
Installation EDUS391000-F12 8. Installation Read these SAFETY CONSIDERATIONS for Installation carefully before installing an air conditioner or heat pump. After completing the installation, make sure that the unit operates properly during the startup operation. Instruct the customer on how to operate and maintain the unit. Inform customers that they should store this Installation Manual with the Operation Manual for future reference. Always use a licensed installer or contractor to install this product.
EDUS391000-F12 parts other than those specified by Daikin are used, fire or explosion may occur. CAUTION • Do not touch the switch with wet fingers. Touching a switch with wet fingers can cause electric shock. • Do not allow children to play on or around the unit to prevent injury.
Installation 2. EDUS391000-F12 FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED. BEFORE INSTALLATION WARNING • Entrust installation to the place of purchase or a qualified serviceman. Improper installation could lead to leaks and, in worse cases, electric shock or fire. • Use of unspecified parts could lead to the unit falling, leaks and, in worse cases, electric shock or fire. NOTE • Be sure to read this manual before installing the indoor unit.
EDUS391000-F12 Installation • Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the installation manual for the outdoor unit.) • If a return-air duct is not installed, carefully select the place and method of product installation so that air flow into the product will not be blocked. WARNING • When installing the unit horizontally, be sure to tilt the unit in the direction shown in Fig. 1-2. If the unit is tilted in any other way, water can leak.
Installation EDUS391000-F12 Table 1 Model 12 · 18 type 24 · 30 · 36 · 42 · 48 · 54 type (4) Check if the unit is horizontally level. A 463/4 531/4 B 22 24 C 171/2 D 191/2 20 22 E 10 12 F G H I 14- 11- 17- 171/2 15/16 1/8 15/16 14- 11- 19- 191/2 15/16 5/8 15/16 (2) Make sure the range of the unit’s external static pressure is not exceeded. (up to 0.5 in.W.C. at “H” speed.) CAUTION • Make sure the unit is installed level using a level tube: four sides.
EDUS391000-F12 5. Installation REFRIGERANT PIPING WORK 〈Observe the requirements listed below for refrigerant piping sizes.〉 Liquid Gas 12 · 18 type 1/4 in. 1/2 in. 24 · 30 · 36 · 42 · 48 · 54 type 3/8 in. 5/8 in. 〈Execute heat insulation work completely on both sides of the gas piping and the liquid piping or else a water leakage might result. Failing to insulate the pipes may cause leaking or burns.
Installation EDUS391000-F12 (1) Install drain piping as described Fig. 6. CAUTION • Be sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping may cause condensation or burns if touched. In case of vertical installation • When brazing the refrigerant piping, perform nitrogen replacement first, or perform the brazing while feeding nitrogen into the refrigerant piping. (Refer to Fig.
EDUS391000-F12 Installation • To keep the piping from becoming clogged with dirt, avoid bends where possible and install so that traps can be cleaned. Air handler At least 4 in. At least 3 in. Fig. 7 • Observe the following guidelines when installing concentrated drain piping. Select the thickness of the concentrated drain piping to reflect the capacity of the machine to which it will be connected. (Install a drain trap for each indoor unit.) (Refer to Fig.
Installation EDUS391000-F12 NOTES 1. If the wiring is in a place where people it can be easily touched by people, install a ground-fault circuit interrupter to prevent electric shock. 2. When using a ground-fault circuit interrupter, make sure to select one useful also to protection against overcurrent and short-circuit. When using a ground-fault circuit interrupter only for grounding device, make sure to use a wiring interrupter together.
EDUS391000-F12 Installation in Fig. 10. • Then secure them in place with the included clamp material (1) as shown in Fig. 10 to protect them from external force from outside the unit. • If the power supply voltage is 208V, change the transformer wire connection from the 240V terminal to the 208V terminal. (Refer to Fig. 11) How to use insulation tube. • Use the insulation tube to cover the wiring. • Joint the insulation tube with the tape and cut off the tube sticking out of the unit.
Installation EDUS391000-F12 • Outside the air conditioners, separate the low voltage wiring (remote controller and transmission wiring) and high voltage wiring (ground wire and power supply wiring) by at least 5 in. so that they do not pass through the same place together. Proximity may cause electrical interference, malfunctions, and breakage. [ PRECAUTIONS ] • Refer to the “REMOTE CONTROLLER INSTALLATION MANUAL” on how to install and lay the wiring for the remote controller.
EDUS391000-F12 Installation Wiring Method (See ‘‘8. ELECTRIC WIRING WORK’’) 10. FIELD SETTING AND TEST RUN (3) Remove the electric component box cover. 〈Field settings may have to be performed using the remote controller, depending on the type of installation.〉 (4) Add remote controller 2 (SUB) to the terminal block for remote controller (P¹, P²) in the electric component box. (There is no polarity.
Installation EDUS391000-F12 (2) Insert the air filter as far as it can go. 10-2 REMOTE CONTROL SETTING • Forced off and ON/OFF operation should be selected by selecting the SECOND CODE NO. as shown in Table 4. Table 4 External ON/OFF input Mode No. Forced off ON/OFF operation 12 (22) FIRST SECOND CODE NO. CODE NO. 01* 1 02 * factory set • Input A of forced off and ON/OFF operation work as shown in Table 5.
EDUS391000-F12 Installation (1) Turn off power supply to all indoor and outdoor units. (2) Remove the front panel (upper) and the electric heater slot cover. (5) Install the circuit breaker mounting bracket removed in step (3) into the blower deck. * The HKR-03 and HKR-06 have no circuit breaker mounting bracket; Procure and install a circuit breaker. Electric heater slot cover (6) Connect the relay connector of the heater kit to the relay connector of the product.
Installation EDUS391000-F12 (8) Pass the power supply wiring and the ground wire through the conduit (conduit should be field supplied). The hole for running wires through should be sealed completely to prevent air from entering. (11) Confirm that there are no mistakes with the wiring, and install the front panel (upper).
EDUS391000-F12 Installation (12) -2 Electric heater operating mode setting 〈When electric heater is used in “Heat Pump lockout mode”〉 • Check the heater capacity. (Select heater marked with “ ” or “ 2” in Table 8.) • Perform on-site setting using the remote controller. • Set the “heat pump lockout mode” using the outdoor unit. (Refer to the service manual for the outdoor unit.) 〈When used as “Auxiliary electric heater”〉 • Check the heater capacity. (Select heater marked with “ 1” in Table 8.
Installation EDUS391000-F12 〈When using a wireless remote controller〉 • A wireless remote controller address needs to be set when using a wireless remote controller. See the installation manual included with the wireless remote controller for details on how to make the settings. Perform a test run according to the outdoor unit’s installation manual. • The operation lamp of the remote controller will flash when a malfunction occurs.
EDUS391000-F12 Accessories 9. Accessories Standard Accessories Name Clamp material (1) Insulation tube Quantity 4 pcs. 1 set (Other) • Operation manual • Installation manual Shape Small (2) 2 pcs. Large (3) 2 pcs. 3P250363-2B Optional Accessories (For Controls): Refer to booklet of “Controls”. Optional Accessories (For Unit) FXTQ~PAVJU No.
Accessories 32 EDUS391000-F12 FXTQ-PA
Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or retailer whether this product conforms tot he applicable standards, and is suitable for use, in the region where the product will be used.