Service manual
6L(1 3URWHFWLRQ&RQWURO
)XQFWLRQ
'LVFKDUJH3LSH3URWHFWLRQ&RQWURO
7KLVGLVFKDUJHSLSHSURWHFWLRQFRQWUROLVXVHGWRSURWHFWWKHFRPSUHVVRULQWHUQDOWHPSHUDWXUH
DJDLQVWDPDOIXQFWLRQRUWUDQVLHQWLQFUHDVHRIGLVFKDUJHSLSHWHPSHUDWXUH
(DFKFRPSUHVVRUSHUIRUPVWKHGLVFKDUJHSLSHWHPSHUDWXUHSURWHFWLRQFRQWUROLQGLYLGXDOO\
LQWKHIROORZLQJVHTXHQFH
>,19FRPSUHVVRU@
>67'FRPSUHVVRU@
HTdi>110°C
Tp>115°C
INV62 Hz + OFF + OFF
HTdi>110°C
Tp>115°C
or
HTdi<105°C
Tp<115°C
&
HTdi>130°C
HTdi>115°C
Tp>130°C
HTdi<95°C
Tp<100°C
&
HTdi : Value of INV compressor discharge pipe
temperature (Tdi) compensated
withoutdoor air temperature
Tp : Value of compressor port temperature
calculated by Tc and Te, and suction
superheated degree.
Discharge pipe temp.
protection control not limited
INV upper limit frequency:
1-step down from current
compressor frequency
In discharge pipe temp.
protection control
When occurring 3 times within 100 minutes,
the malfunction code “F3” is output.
Discharge pipe
temp.control standby
INV upper limit frequency: 1-step up
from current compressor frequency
Every 60 sec.
Every 30 sec.
or
or
for 90 sec.
or more.
HTdi>135°C
HTdi>115°C for 10 min. or more.
Applicable STD
compressor stops.
• HTds>115°C continues for 5 min. or more.
• HTds>135°C
• Tp>115°C continues for 10 min. or more.
• Tp>130°C
Discharge pipe temp.
protection control not limited
10 min.
or
HTds: Value of STD compressor discharge
pipe temperature (Tds) compensated
with outdoor air temperature
Tp: Value of compressor port temperature
calculated by Tc
and
Te, and suction
superheated degree.