Connector of fan
motor is
disconnected.
Harness
connector
between
compressor inverter
PCB and fan inverter PCB
(A2P, A3P) is
disconnected.
YES
Can the fan be turned
smoothly with hand after
disconnect the connector
of fan motor?
Is there any obstacle
around the fan?
NO
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
YES
YES
YES
NO
NO
NO
Connect the connector.
Connect the harness
connector.
Remove the obstacle.
Replace the fan motor of
outdoor unit.
(V3076)
1A