EDUS 39 - 900A - F11_a FXMQ-M Ceiling Mounted Duct Unit AMERICAS
EDUS39-900A-F11_a FXMQ-M Ceiling Mounted Duct Unit 1. 2. 3. 4. 5. 6. 7. External Appearance...................................................................................2 Specifications ..............................................................................................3 Dimensions .................................................................................................4 Piping Diagrams..........................................................................................
External Appearance EDUS39-900A-F11_a 1.
EDUS39-900A-F11_a Specifications 2. Specifications Ceiling Mounted Duct Unit Model FXMQ72MVJU FXMQ96MVJU 1 Cooling Capacity Btu/h 72,000 96,000 2 Heating Capacity Btu/h 81,000 108,000 Galvanized Steel Plate Galvanized Steel Plate in.
Dimensions EDUS39-900A-F11_a 3.
EDUS39-900A-F11_a Piping Diagrams 4.
Wiring Diagrams EDUS39-900A-F11_a 5.
EDUS39-900A-F11_a Electric Characteristics 6. Electric Characteristics Units Model FXMQ72MVJU FXMQ96MVJU Power supply IFM Input (W) Hz Volts Voltage range MCA MOP kW FLA Cooling Heating 60 208-230 MAX. 253 MIN. 187 9.5 15 0.380 x 2 7.6 1,490 1,490 10.7 15 0.380 x 2 8.6 1,684 1,684 NOTES: 1. Voltage range: Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. 2.
Capacity Tables EDUS39-900A-F11_a 7. Capacity Tables 7.1 Cooling Capacity FXMQ72MVJU Cooling capacity Indoor (FWB) Outdoor FDB 75 79 83 87 91 95 99 103 61 TC 56.9 56.9 56.9 56.9 56.9 56.9 56.9 56.9 64 SHC 50.8 50.8 50.8 50.8 50.8 50.8 50.8 50.8 TC 64.4 64.4 64.4 64.4 64.4 64.4 64.4 64.4 67 SHC 53.9 53.9 53.9 53.9 53.9 53.9 53.9 53.9 TC 72.0 72.0 72.0 72.0 72.0 72.0 70.7 69.4 70 SHC 56.9 56.9 56.9 56.9 56.9 56.9 56.9 56.9 TC 79.5 78.8 77.3 75.8 74.7 73.4 72.2 70.8 72 SHC 60.1 60.1 60.1 60.1 60.
EDUS39-900A-F11_a 7.2 Capacity Tables Heating Capacity FXMQ72MVJU Heating capacity Indoor (FDB) Outdoor FDB 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 FWB 20.0 24.0 28.0 32.0 36.0 40.0 43.0 47.0 50.0 53.0 56.0 62 TC 72.2 76.5 81.0 85.5 90.8 94.5 94.5 94.5 94.5 94.5 94.5 65 TC 72.1 76.5 81.0 85.5 88.5 88.5 88.5 88.5 88.5 88.5 88.5 68 TC 71.9 75.8 80.3 84.0 84.0 84.0 84.0 84.0 84.0 84.0 84.0 70 TC 71.9 75.8 80.3 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 72 TC 71.8 75.8 78.0 78.0 78.0 78.
Fan Performances EDUS39-900A-F11_a 8. Fan Performances FXMQ72MVJU Notes: 1. The remote controller can be used to switch between “high” and “low”. 2. The air flow is set to “standard” before leaving the factory. It is possible to switch between “standard ESP” and “high ESP” by changing the switch in the indoor unit electrical box.
EDUS39-900A-F11_a Fan Performances FXMQ96MVJU Notes: 1. The remote controller can be used to switch between “high” and “low”. 2. The air flow is set to “standard” before leaving the factory. It is possible to switch between “standard ESP” and “high ESP” by changing the switch in the indoor unit electrical box.
Sound Levels (Reference) EDUS39-900A-F11_a 9. Sound Levels (Reference) 9.1 Overall Location of microphone 3.3 ft DUCT DUCT SUCTION 4.9 ft DISCHARGE 6.6 ft MICROPHONE Notes: 1. The operating conditions are assumed to be standard (JIS conditions). Power source 208-230V, 60hz. 2. The operating values were obtained in an anechoic chamber (conversion values). 3.
EDUS39-900A-F11_a Center of Gravity 10.
Installation EDUS39-900A-F11_a 11. Installation 1. SAFETY CONSIDERATIONS Read these “SAFETY CONSIDERATIONS for Installation” carefully before installing air conditioning equipment. After completing the installation, make sure that the unit operates properly during the startup operation. Instruct the customer on how to operate and maintain the unit. Inform customers that they should store this Installation Manual with the Operation Manual for future reference.
EDUS39-900A-F11_a • Do not change the setting of the protection devices. If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by Daikin are used, fire or explosion may occur. CAUTION • Do not touch the switch with wet fingers. Touching a switch with wet fingers can cause electric shock. • Do not allow children to play on or around the unit to prevent injury.
Installation 2. BEFORE INSTALLATION • When moving the unit while removing it from the carton box, be sure to lift it by holding on to the four lifting lugs without exerting any pressure on other parts, especially, the refrigerant piping, drain piping, and other resin parts. • Be sure to check the type of R410A refrigerant to be used before installing the unit. (Using an incorrect refrigerant will prevent normal operation of the unit.
EDUS39-900A-F11_a Installation b. Items to be checked at time of delivery Also review the “SAFETY CONSIDERATIONS” Items to be checked Check Did you explain about operations while showing the instruction manual to your customer? (2) Use suspension bolts for installation. Check whether the ceiling is strong enough to support the weight of the unit or not. If there is a risk, reinforce the ceiling before installing the unit. 18-1/2 Did you hand the instruction manual over to your customer? c.
Installation EDUS39-900A-F11_a (3) Install suspension bolts. (Use bolts of 3/8in. diameter.) • Install the equipment where supporting structures are strong enough to bear the equipment’s weight. Use embedded inserts or anchor bolts with new buildings and hole-in-anchors with old buildings. Installation example Ceiling slab Anchor Long nut or turn-buckle Suspension bolt Indoor unit Note) All the above parts are field supplied. 5.
EDUS39-900A-F11_a Installation NOTE The flare nuts used must be those included with the main body. Ester oil or ether oil. • Connect refrigerant piping and branching according to the attached installation manuals that come with the outdoor unit. Indoor units to be connected Gas piping diameter FXMQ72MVJU φ3/4 Use attached piping. FXMQ96MVJU φ7/8 Use attached piping.
Installation 7. EDUS39-900A-F11_a DRAIN PIPING WORK Rig the drain pipe as shown below and take measures against condensation. Improperly rigged piping could lead to leaks and eventually wet furniture and belongings. Insulate the drain hose inside the building. (1) Carry out the drain piping. • A drain trap need not be installed. • The diameter of the piping is the same as that of the connecting pipe (PS1B), and should be kept equal to or greater than that of the connecting pipe.
EDUS39-900A-F11_a 8-3 Installation SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power supply wiring Model Breaker FXMQ72MVJU 15A FXMQ96MVJU Size Size must comply with local codes. Remote controller wiring Transmission wiring Wire Size 2-conductor, stranded nonshielded copper cable/ PVC or vinyl jacket AWG 18-2, Max: 1640 ft. Power supply wiring Clamp or (accessory (8)) Transmission wiring Insulation tube (accessory (2)) (3in.
Installation EDUS39-900A-F11_a 2. Tightening torque for the terminal screws. • Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is too small, the head of the screw might be damaged, and the screw will not be properly tightened. • If the terminal screws are tightened too hard, screws might be damaged. • Refer to the table below for the tightening torque of the terminal screws. 1. When using 1 remote controller for 1 indoor unit.
EDUS39-900A-F11_a 9-3 Installation CONTROL BY 2 REMOTE CONTROLLERS (Controlling 1 indoor unit by 2 remote controllers) • When using 2 remote controllers, one must be set to “MAIN” and the other to “SUB”. 9-4 COMPUTERISED CONTROL (FORCED OFF AND ON/OFF OPERATION) (1) Wire specifications and how to perform wiring • Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller.
Installation EDUS39-900A-F11_a 10. FIELD SETTING Make sure the terminal box lids are closed on the indoor and outdoor units. Field setting must be made from the remote controller in accordance with the installation condition. • Setting can be made by changing the “Mode No.”, “FIRST CODE NO.”, and “SECOND CODE NO.”. • For setting and operation, refer to the “FIELD SETTING” in the installation manual of the remote controller. SECOND CODE NO. MODE NO. FIRST CODE NO.
EDUS39-900A-F11_a Accessories 12. Accessories Standard Accessories Name Attached piping (1) Insulation tube (2) Quantity 1 set 2 pcs. Shape (Other) (3) Operation manual (4) Installation manual (5) Screws for flange connection (M5) (48 pcs.) (6) Insulation material (for hanger) (2 pcs.) (7) Washers (8 pcs.) (8) Clamps (6 pcs.) (9) Hexagon head bolt for pipe frange (M10) (2 pcs.) (10) Spring washer for pipe frange (M10) (2 pcs.
Accessories 26 EDUS39-900A-F11_a FXMQ-M
AMERICAS 1645 Wallace Drive, Suite 110 Carrollton, TX75006 info@daikinac.com www.daikinac.com August 2010 EDUS39-900A-F11_a Printed in U.S.A. 08/10 AK·FS.