EDUS39-600-F3_b FXSQ-M Ceiling Mounted Built-In Type 1. 2. 3. 4. 5. 6. 7. Features ......................................................................................................2 Specifications ..............................................................................................5 Dimensions .................................................................................................7 Piping Diagrams.......................................................................................
Features EDUS39-600-F3_b 1. Features A The Ceiling Mounted Built-In Type is a highly flexible air-conditioning system adaptable to a wide range of needs and is designed to facilitate maintenance while providing a high quality environment. Offers a wide variety of optional functions, giving you the freedom to choose the best setup for both interior design and convenient maintenance. All models feature thin design (11 7/8" height) that enable installation in shallow ceiling pockets. .
EDUS39-600-F3_b Features Example of Installation (Built-In) Direct installation of half panel Model Necessary Options FXSQ18M BYBS32DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 FXSQ12M FXSQ18M FXSQ24M FXSQ30M FXSQ36M FXSQ48M Half Panel BYBS32DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 Air Suction Canvas KSA-25K36 KSA-25K56 KSA-25K80 KSA-25L160 FXSQ12M FXSQ18M FXSQ24M FXSQ30M FXSQ36M FXSQ48M BYBS32DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 NBS65% KAFJ252L36 KAFJ252L56 KAFJ252L80 KAFJ252
Features EDUS39-600-F3_b Ceiling return Model Necessary Options FXSQ18M KTBJ25K36W KTBJ25K56W KTBJ25K80W KTBJ25K160W FXSQ12M FXSQ18M FXSQ24M FXSQ30M FXSQ36M FXSQ48M Access Panel KTBJ25K36W KTBJ25K56W KTBJ25K80W KTBJ25K160W Screening Door KBBJ25K36 KBBJ25K56 KBBJ25K80 KBBJ25K160 Air Suction Flange KDJ2507K36 KDJ2507K56 KDJ2507K80 KDJ2507K160 Remote Controller Access Panel FXSQ24M FXSQ30M FXSQ36M FXSQ48M FXSQ12M BRC1D71 The access panel should be fitted beneath the main body
EDUS39-600-F3_b Specifications 2. Specifications Ceiling Mounted Built-In Type FXSQ12MVJU FXSQ18MVJU FXSQ24MVJU Cooling Capacity1 Model Btu/h 12,000 18,000 24,000 Heating Capacity2 Btu/h 13,500 20,000 27,000 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate in (mm) 11-7/8 × 21-5/8 × 31-1/2 (301.6 x 549.3 x 800.1) 11-7/8 × 27-1/2 × 31-1/2 (301.6 x 698.5 x 800.1) 11-7/8 × 39-3/8 × 31-1/2 (301.6 x 1000.1 x 800.1) 3 × 4 × 14 3 × 4 × 14 3 × 14 × 14 ft² (m²) 0.95 (0.
Specifications EDUS39-600-F3_b Ceiling Mounted Built-In Type Model FXSQ30MVJU FXSQ36MVJU FXSQ48MVJU Cooling Capacity1 Btu/h 30,000 36,000 48,000 Heating Capacity2 Btu/h 34,000 40,000 54,000 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 11-7/8 × 50-1/8 × 31-1/2 (301.6 x 1273.2 x 800.1) 11-7/8 × 50-1/8 × 31-1/2 (301.6 x 1273.2 x 800.1) 11-7/8 × 50-1/8 × 31-1/2 (301.6 x 1273.2 x 800.1) 3 × 4 × 14 3 × 4 × 14 3 × 14 × 14 3.64 3.64 3.
EDUS39-600-F3_b Dimensions 3.
Dimensions EDUS39-600-F3_b 3D042525 FXSQ18MVJU + BYBS45DJW1 (with Decoration Panel and Air Suction Canvas) 8 FXSQ-M
EDUS39-600-F3_b Dimensions 3D042526 FXSQ24MVJU + BYBS71DJW1 (with Decoration Panel and Air Suction Canvas) FXSQ-M 9
Dimensions EDUS39-600-F3_b 3D042527 FXSQ30MVJU + BYBS125DJW1 (with Decoration Panel and Air Suction Canvas) FXSQ36MVJU + BYBS125DJW1 (with Decoration Panel and Air Suction Canvas) FXSQ48MVJU + BYBS125DJW1 (with Decoration Panel and Air Suction Canvas) 10 FXSQ-M
EDUS39-600-F3_b Dimensions 3D042520 FXSQ12MVJU FXSQ-M 11
Dimensions EDUS39-600-F3_b 3D042521 FXSQ18MVJU 12 FXSQ-M
EDUS39-600-F3_b Dimensions 3D042522 FXSQ24MVJU FXSQ-M 13
Dimensions EDUS39-600-F3_b 3D042523 FXSQ30MVJU FXSQ36MVJU FXSQ48MVJU 14 FXSQ-M
EDUS39-600-F3_b Piping Diagrams 4.
Wiring Diagrams EDUS39-600-F3_b 5.
EDUS39-600-F3_b Electric Characteristics 6.
Capacity Tables EDUS39-600-F3_b 7. Capacity Tables 7.1 Cooling Capacity FXSQ-M Cooling capacity Indoor Air Temp. °FWB Unit size Outdoor air temp. °FDB 12 18 24 30 36 48 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 61 64 67 70 72 75 TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 14.2 14.
EDUS39-600-F3_b 7.2 Capacity Tables Heating Capacity FXSQ-M Heating Capacity Indoor Air Temp. °FDB Indoor unit Outdoor Air Temp. °FDB 12 18 24 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 °FWB 20.0 24.0 28.0 32.0 36.0 40.0 43.0 47.0 50.0 53.0 56.0 20.0 24.0 28.0 32.0 36.0 40.0 43.0 47.0 50.0 53.0 56.0 20.0 24.0 28.0 32.0 36.0 40.0 43.0 47.0 50.0 53.0 56.
Capacity Tables EDUS39-600-F3_b Heating Capacity Indoor Air Temp. °FDB Indoor unit Outdoor Air Temp. °FDB 30 36 48 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 °FWB 20.0 24.0 28.0 32.0 36.0 40.0 43.0 47.0 50.0 53.0 56.0 20.0 24.0 28.0 32.0 36.0 40.0 43.0 47.0 50.0 53.0 56.0 20.0 24.0 28.0 32.0 36.0 40.0 43.0 47.0 50.0 53.0 56.
EDUS39-600-F3_b Fan Performances 8. Fan Performances FXSQ12MVJU FXSQ18MVJU WG FXSQ24MVJU WG WG FXSQ30MVJU FXSQ36MVJU WG FXSQ48MVJU WG WG Note: 1. The remote controller can be used to switch between HIGH and LOW. 2. The airflow is set to STANDARD before leaving the factory. It is possible to switch between STANDARD ESP and HIGH ESP by changing the terminals in the indoor unit electrical box. 3.
Sound Levels EDUS39-600-F3_b 9. Sound Levels Overall Ceiling Mounted Built-In Type Notes: Operation noise differs with operation and ambient conditions.
EDUS39-600-F3_b Installation 10. Installation Center of Gravity MODEL FXSQ12MVJU FXSQ18MVJU FXSQ24MVJU FXSQ30, 36, 48MVJU A 21-5/8 27-1/2 39-3/8 55-1/8 B 9-7/8 11-3/4 18-1/8 25-1/4 4D042534 1. SAFETY CONSIDERATIONS Read these SAFETY CONSIDERATIONS carefully before installing air conditioning equipment, and be sure to install it correctly. After completing the installation, make sure that the unit operates properly during the start-up operation.
Installation • Do not touch the air outlet or the horizontal flaps while the swing flap is in operation as fingers may get caught and injured. • Install the air conditioner on a foundation strong enough to withstand the weight of the unit. A foundation of insufficient strength may result in the equipment falling and causing injuries. • Carry out the specified installation work after taking into account strong winds, typhoons, or earthquakes.
EDUS39-600-F3 Installation • Dismantling of the unit, and treatment of the refrigerant, oil, and other parts, should be done in accordance with the relevant local and national regulations.
Installation 2. BEFORE INSTALLATION • When moving the unit while removing it from the packing case, be sure to lift it by the four hanger brackets. Avoid putting any pressure on other parts especially the refrigerant piping. • When moving the unit while removing it from the packing case, be sure to lift it by the four hanger brackets. Avoid putting any pressure on other parts, especially the refrigerant piping.
EDUS39-600-F3 Installation Table 2 Remote controller Wired type BRC1D71 FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED. a. Items to be checked after completion of work Items to be checked The following problems may occur If not properly done: Are the indoor and outdoor unit fixed firmly? Units may drop, vibrate, or make noise. Is the gas leak test finished? May result in insufficient cooling.
Installation EDUS39-600-F3 (Optional accessory) 18 1/8 Ceiling surface Indoor unit (Back side) Suspension bolt pitch B A 5 11/16 24 13/16 A (Ceiling opening) (length : in.) Model A (in.) FXSQ12MVJU 24 FXSQ18MVJU 29 7/8 FXSQ24MVJU 41 11/16 FXSQ30 · 36 · 48MVJU 57 7/16 Suspension bolt (× 4) For mounting air inlet panel directly, use the following diagram: (length : in.) 31 1/2 7 1/16 Model A (in.) B (in.
EDUS39-600-F3 Installation 5. Installation example Ceiling slab Anchor Long nut or turn-buckle Suspension bolt Indoor unit Note: All the above parts are field supplied. (3) Install the suspension bolts using bolts of 3/8” diameter. Use a hole-in-anchor, sunken insert, sunken anchor for existing ceilings, and use a sunken insert, sunken anchor, or other part to be procured in the field to reinforce the ceiling to bearthe weight of the unit.
Installation 6. EDUS39-600-F3 REFRIGERANT PIPING WORK 6-1 NOTE GENERAL INSTRUCTIONS • To install refrigerant piping to outdoor units, see the installation manual attached to the outdoor unit. • Before performing refrigerant piping work, check which type of refrigerant is used. Proper operation is not possible if the types of refrigerant are not the same. • Make sure the outdoor unit is charged with refrigerant. NOTE • Use a pipe cutter and flare suitable for the type of refrigerant.
EDUS39-600-F3 Installation 7. Insulation for fitting (accessory) Clamp (× 4 accessory) (For liquid pipe) Liquid pipe Gas pipe Mid sealing pad (accessory) Insulation for fitting (accessory) (For gas pipe) DRAIN PIPING WORK Install the drain pipe as shown below and take measures against condensation. Improperly installed piping could lead to leaks on furniture and belongings. (1) Install the drain piping.
Installation EDUS39-600-F3 ≥3 15/16” • If converging multiple drain pipes, install according to the procedure shown below. WHEN ELECTRIC WIRING WORK IS FINISHED: • Check drainage flow during COOL running, explained under TEST OPERATION. WHEN ELECTRICAL WIRING WORK IS NOT FINISHED: T-joint converging drain pipes • Remove the electric parts box lid, connect a power supply and remote controller to the terminals.
EDUS39-600-F3 8-2 Installation 9. ELECTRICAL CHARACTERISTICS Power supply Units Model Hz VoltVolts age MCA MFA range Fan motor 9-1 W FLA FXSQ12MVJU 0.7 15 50 0.6 FXSQ18MVJU 1.0 15 85 0.8 1.4 15 125 1.1 1.8 15 225 1.4 1.8 15 225 1.5 2.4 15 225 2.0 FXSQ24MVJU FXSQ30MVJU 60 208230 FXSQ36MVJU Max. 253 Min. 187 FXSQ48MVJU MCA:Min. Circuit Amps (A); MFA:Max.
Installation EDUS39-600-F3 to the terminal block for remote control wiring or it could damange the entire system. • Improper installation can lead to leaks and, in worst cases, electric shock, or fire. 4. Outside of the unit, keep transmission wiring at least 1 15/16” away from power supply wiring. The equipment may malfunction if subjected to electrical (external) noise. Adaptor for PC board View as seen from A CAUTION NOTE 1.
EDUS39-600-F3 9-2 Installation SETTING OF STATIC PRESSURE CHANGEOVER CONNECTOR • According to the system static pressure requirement, reposition the adaptors of PC board inside the electric parts box as shown in the following drawings. Static pressure Model Standard X4A X5A Low Black X3A X7A X6A Low High Blue X4A X3A X7A Standard Low X5A FXSQ12. 18 . 24MVJU X6A Standard High Blue Black Standard X4A X5A Low X3A X7A X6A High High Black Blue Low Not available FXSQ30 .
Installation 9-3 EDUS39-600-F3_b WIRING EXAMPLE • Fit the power supply wiring of each unit with a switch and fuse as shown in the drawing. COMPLETE SYSTEM EXAMPLE Power supply wiring Transmission wiring Power supply Main switch NOTE 1. A single switch can be used to supply power to units on the same system. However, branch switches and branch circuit breakers must be selected carefully. 2. Do not ground the equipment on gas pipes, water pipes or lightning rods, or crossground with telephones.
EDUS39-600-F3_b 9-5 Installation COMPUTERIZED CONTROL: FORCED OFF AND ON/OFF OPERATION (1) Wire specifications and how to perform wiring • Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller. 9-6 CENTRALIZED CONTROL • For centralized control, it is necessary to designate the group No. For details, refer to the manual of each optional controller for centralized control. 10.
Installation EDUS39-600-F3_b 11. TEST OPERATION Refer to the installation manual of the outdoor unit. • The operation lamp of the remote controller will flash when a malfunction occurs. Check the malfunction code on the display to identify the problem. An explanation of malfunction codes and the corresponding trouble is provided in the Service Manual for theoutdoor unit. If any of the items in Table are displayed, there may be a problem with the wiring or power, so check the wiring again.
EDUS39-600-F3_b Accessories 11. Accessories Standard Accessories Name Metal clamp Paper pattern for installation Drain hose Insulation for fitting Sealing pad Screws for duct flanges Quantity 1 pc. 1 pc. 1 pc. 1 each. 1 each 1 set for gas pipe Shape for liquid pipe Name Washer for hanging bracket Clamp 8 pcs. 6 pcs. Quantity Screws for fixing the paper pattern for installation 6 pcs. Shape Large mid FXSQ12MVJU 6 FXSQ18MVJU 8 FXSQ24MVJU 12 FXSQ30 . 36 .