Specifications

Installation EDUS39-900A-F4
34 FXMQ-P
(4) Put the control box lid, and wrap the wire sealing material
(Small) (10) around the conduit so as to block the wire
through holes.
After all the wiring connections are done, fill in any gaps in
the through holes with putty or insulation (procured locally)
to prevent small animals and insects from entering the unit
from outside. (If any do get in, they could cause short
circuits in the control box.)
[Precautions for Power Supply Wiring]
Connect round crimp-style terminals provided with
insulation sleeves to the terminal block for power supply.
Be sure to follow the instructions provided below if the
specified terminals cannot be used.
Otherwise, abnormal heat may be generated as a result
of the loosening of the wires.
If stranded wires are used, do not solder the front end of the
wires.
Connect proper wires securely and fix the wires so that
external force will not be imposed on the terminals.
Use an appropriate screwdriver to tighten the terminal
screws. The screw heads may be damaged if the
screwdriver is too small and the terminal screws will not be
tightened properly.
Do not tighten the terminal screws excessively, or
otherwise the screw heads may be damaged.
Refer to the table below for the required tightening torque
values of the terminal screws.
Tightening torque (lbf·ft)
Terminal block for remote controller
and transmission wires
0.58 - 0.72
Wire through holes
Electric wire
Round crimp-style terminal
Attach insulation sleeve
Connect the wires
evenly.
Do not connect a
wire to the single
side only.
Do not connect
wires different
from each other in
diameter.
Terminal block for power supply
Ground wiring
0.87 - 1.06