Specifications

Specifications EDUS39-900A-F4
2 FXMQ-P
1. Specifications
Ceiling Mounted Duct Type
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Standard external static pressure
Equivalent ref. piping length: 25ft (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Standard external static pressure
Equivalent ref. piping length: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 External static pressure is changeable in 7 (FXMQ07, 09, 12PVJU), 14 (FXMQ18, 24, 30, 36PVJU), 10 (FXMQ48PVJU) stages within the ( )
range by remote controller.
5 Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its colorimetric method (gravity method) 50% or more.
6 Refer to page 11 for Power Input.
Model FXMQ07PVJU FXMQ09PVJU FXMQ12PVJU
1, 3 Cooling Capacity Btu/h 7,500 9,500 12,000
2, 3 Heating Capacity Btu/h 8,500 10,500 13,500
Casing / Color Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D) in 11-13/16
× 21-5/8 × 27-9/16 11-13/16 × 21-5/8 × 27-9/16 11-13/16 × 21-5/8 × 27-9/16
Coil (Cross
Fin Coil)
Rows×Stages×FPI 3×16×15 3×16×15 3×16×15
Face Area ft² 1.05 1.05 1.05
Fan
Model
Type Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output W 90 90 90
Air Flow Rate (HH/H/L) cfm 317/264/229 317/264/229 335/282/246
External Static Pressure in. H
2O Standard 0.20 (0.40-0.12
4
) Standard 0.20 (0.40-0.12
4
) Standard 0.20 (0.40-0.12
4
)
Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat for Cooling
and Heating
Microprocessor Thermostat for Cooling
and Heating
Microprocessor Thermostat for Cooling
and Heating
Air Filter 5— 5— 5
Piping
Connections
Liquid Pipes in 1/4 (Flare Connection) 1/4 (Flare Connection) 1/4 (Flare Connection)
Gas Pipes in 1/2 (Flare Connection) 1/2 (Flare Connection) 1/2 (Flare Connection)
Drain Pipe in
VP25
External Dia. 1-1/4
Internal Dia. 1
VP25
External Dia. 1-1/4
Internal Dia. 1
VP25
External Dia. 1-1/4
Internal Dia. 1
Mass (Weight) Lbs 55 55 55
Safety Devices
Fuse,
Fan Driver Overload Protector
Fuse,
Fan Driver Overload Protector
Fuse,
Fan Driver Overload Protector
Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Connectable outdoor unit R-410A Series R-410A Series R-410A Series
Standard Accessories
Operation Manual, Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Screws, Insulation for Fitting,
Clamp Metal, Air Discharge Flange, Air
Suction Flange
Operation Manual, Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Screws, Insulation for Fitting,
Clamp Metal, Air Discharge Flange, Air
Suction Flange
Operation Manual, Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Screws, Insulation for Fitting,
Clamp Metal, Air Discharge Flange, Air
Suction Flange
Drawing No. 3D066117B
(
)
(
)
(
)