Specifications

EDUS39-900A-F4 Airflow Auto Adjustment Characteristics
FXMQ-P 19
Notes:
1. To offset the reduction in airflow volume from the rated value, it is possible to adjust the airflow volume up to 10%
using the Airflow Auto-Adjustment function during installation and commissioning.
2. After completing the installation of the indoor unit ductwork, use the remote controller to set the airflow
auto-adjustment.
3. For instructions on how to set the Airflow Auto-Adjustment, refer to the Installation Manual attached to the indoor
unit.
4. External static pressure of 0.2 to 0.8” Wg can be adjusted by the Airflow Auto-Adjustement function if airflow is HH.
5. If the auto-adjustment function is not utilized, the airflow rate will be in accordance with the fan’s characteristics
shown above.
6. This figure shows a fan’s characteristics at the time of "HH" "H" and "L".
7. The remote controller can be used to change "HH" "H" and "L".
8. ESP : external static pressure.
9. Please set the external static pressure of the suction duct at 0.6” Wg or less.