Specifications

Airflow Auto Adjustment Characteristics EDUS39-900A-F4
18 FXMQ-P
8. Airflow Auto Adjustment Characteristics
Notes:
1.To offset the reduction in airflow volume from the rated value, it is possible to adjust the airflow volume up to 10% using
the Airflow Auto-Adjustment function during installation and commissioning
2. After completing the installation of the indoor unit ductwork, use the remote controller to set the airflow
auto-adjustment.
3. For instructions on how to set the Airflow Auto-Adjustment, refer to the Installation Manual attached to the indoor
unit.
4. External static pressure of 0.12 to 0.4” Wg can be adjusted by the Airflow Auto-Adjustement function if airflow is
HH.
5. If the Auto-Adjustment Function is not utilized, the airflow rate will be in accordance with the fan characteristics
shown above.
6. This figure shows fan characteristics at the time of "HH" "H" and "L".
7. The remote controller can be used to change "HH" "H" and "L".
8. ESP : external static pressure.
FXMQ07PVJU / FXMQ09PVJU
3D066128A 3D066129B
FXMQ12PVJU