Specifications
SiBE06-708 Control Specification
Function and Control 35
3.3 Controls at Mode Changing / Start-up
3.3.1 Preheating Operation
Outline
25/35 class
Operate the inverter in the open phase operation with the conditions including the preheating
command from the discharge pipe temperature.
50 class
Operate the inverter in the open phase operation with the conditions including the outdoor air
temperature, discharge pipe temperature, and fin temperature (internal temperature of PM1).
Detail
25/35 class
Outside temperature ≥ 10°C → Control A (preheating for normal state)
Outside temperature < 10°C → Control B (preheating of increased capacity)
Control A
ON condition
Discharge pipe temperature < 10°C
Fin temperature < 85°C
OFF condition
Discharge pipe temperature > 12°C
Fin temperature ≥ 90°C
Control B
ON condition
Discharge pipe temperature < 20°C
Fin temperature < 85°C
OFF condition
Discharge pipe temperature > 22°C
Fin temperature ≥ 90°C
50 class
Outside temperature ≥ 10°C → Control A (preheating for normal state)
Outside temperature < 10°C → Control B (preheating of increased capacity)
Control A
ON condition
Discharge pipe temperature < 6°C
Fin temperature < 85°C
OFF condition
Discharge pipe temperature > 8°C
Fin temperature ≥ 90°C
Control B
ON condition
Discharge pipe temperature < 10.5°C
Fin temperature < 85°C
OFF condition
Discharge pipe temperature > 12°C
Fin temperature ≥ 90°C
Note: The power consumption of compressor during preheat operation is 35 W.