Specifications

SiBE06-708 Others
Others 189
1.2 Jumper Settings
1.2.1 When Two Units are Installed in One Room
When two indoor units are installed in one room, the two wireless remote controllers can be set
for different addresses.
How to set the different addresses
1) Remove the front grille.
2) Live the sensor securing plate and remove the front metal plate cover.
3) Remove connectors 5P, 6P, and 7P.
4) Remove the electric box (1 screw).
5) Remove the thermistor.
6) Remove the side metal plate cover (8 tabs).
7) Cut the address jumper (JA) on the printed circuit board.
8) Cut the address jumper (J4) in the remote controller.
1.2.2 Jumper Setting
3) Connector 6P
5) Thermistor
3) Connector 5P
3) Connector 7P
4) Remove 1 screw.
JA
ADRESS
EXIST
1
CUT 2
JA
2) Front metal plate cover
6) Side metal plate cover
2) Sensor
securing
plate
J4
J4
ADRESS
EXIST
1
CUT 2
(R6840)
Jumper
(On indoor control PCB)
Function When connected
(factory set)
When cut
JC Power failure
recovery function
Auto start Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
JB Fan speed setting
when compressor is
OFF on thermostat.
(effective only at
cooling operation)
Fan speed setting ;
Remote controller
setting
Fan rpm is set to “0”
<Fan stop>