Service manual
Forced Cooling Operation SiBE06-708_C
142 Trial Operation and Field Settings
2. Forced Cooling Operation
Indoor Unit
Outdoor Unit: RK(X)S25/35F2V1B, RK(X)S25/35G2V1B
Outdoor Unit: RK(X)S25/35G2V1B9, RXS25/35J2V1B, RXS25/35K2V1B, RXS25K3V1B
Item Forced Cooling
Conditions The forced cooling operation is allowed when both of the following conditions are
met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start The forced cooling operation starts when any of the following conditions is fulfilled.
1) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit for
5 seconds.
2) Press the forced cooling operation ON/OFF switch (SW1) on the outdoor unit.
Command
frequency
RK(X)S25/35F2V1B, RK(X)S25/35G2V1B: 68 Hz
RK(X)S25/35G2V1B9, RXS25/35J2V1B, RXS25/35K2V1B, RXS25K3V1B: 58 Hz
50 class: 66 Hz
End The forced cooling operation ends when any of the following conditions is fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
again.
3) Press the [ON/OFF] button on the remote controller.
4) Press the forced cooling operation ON/OFF switch (SW1) on the outdoor unit.
Others Protection functions have priority over all other functions during forced cooling
operation.
ON/OFF button
(SW1)
(R14184)
Screwdriver
(R18372)
Push
here
1
2
3
1
2
3
Push here
Screwdriver
(R18256)
Terminal board