Service manual
Troubleshooting SiBE06-708_C
114 Service Diagnosis
4.22 CT or Related Abnormality (RK(X)S50F2V1B,
RK(X)S50G2V1B, RXS50J2V1B Only)
Error Code
H8
Method of Error
Detection
A CT or related error is detected by checking the compressor running frequency and CT-
detected input current.
Error Decision
Conditions
The compressor running frequency is more than A Hz, and the CT input current is less than
B A.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective power module
Broken or disconnected wiring
Defective reactor
Defective outdoor unit PCB
A (Hz) B (A)
55 0.5