Service manual

2-13
2.5.3 Defrosting mode
Start defrosting
Is terminating
condition OK?
Defrost lamp (red) ON
Pump down
Defrosting range
Defrosting lamp (red) OFF
Return to frozen, chilled or partial
frozen operation
Evaporator fan On after delay of 60 seconds
Compressor ON
Evaporator fan OFF
Condenser fan ON/OFF
Defrosting solenoid valve
ON
Hot gas solenoid valve
ON
No
Yes
Yes
Component name Pump down Defrosting
Compressor CC ON ON
Evaporator fan. High speed EFH
ON/OFF3 OFF
Evaporator fan. Low speed EFL
Condenser fan CF
ON/OFF1 ON/OFF1
Liquid solenoid valve LSV OFF OFF
Economizer solenoid valve ESV
ON/OFF4
OFF
Injection solenoid valve ISV
OFF (ON5) ON/OFF2
Hot-gas solenoid valve HSV OFF ON
Defrost solenoid valve DSV OFF ON
Discharge gas by-pass solenoid valve
BSV OFF OFF
Reheat solenoid valve RSV OFF OFF(ON
6)
Suction modulating valve SMV 100% 100%
Electronic expansion valve EV 10 to 100% 5%
Operation of magnetic contactor and solenoid valve
Note) 1: Pressure control
2: Charging control
3: Frozen mode ... EFL ON, Chilled mode ... EFH ON
4: Economizer control
5: Discharge gas temperature control
6: EOS>15˚C
Magnetic
contactor
Solenoid valve