Service manual

State
Malfunction occurrence
Abnormal point Possible cause
C.
Condenser fan rotates,
q Activation of Short circuit of condenser fan motor
but evaporator fan and
high-pressure switch Wrong installation of condenser fan
compressor do not (Water cooled Reverse rotation of condenser fan
rotate. condenser type) Insufficient cooling water flow rate
Water-cooled condenser blocked with scale
w Overcurrent due to overload operation, etc.
e Abnormal low
Electronic expansion valve: poor contact of connector
pressure drop Electronic expansion valve: incorrect opening
Electronic expansion valve: blocked
Suction modulating valve: blocked
Dryer: blocked
r Abnormal discharge Hot gas solenoid valve: coil wire broken
gas temperature Injection solenoid valve: closed
Injection capillary tube: blocked
High pressure increasing due to overload
A. Suction pressure is q
Poor compression of compressor
Abrasion of scroll slide section
high w
Hot gas solenoid valve
Valve leakage
e
Defrosting solenoid valve
Valve leakage
r Discharge gas Valve leakage
by-pass solenoid valve
t
Electronic expansion valve
Electronic expansion valve malfunction
Poor contact of connector
y
Injection solenoid valve
Valve leakage
B. Suction pressure is q
Liquid solenoid valve (Not opened)
Solenoid valve coil malfunction
excessively low w
Shortage of refrigerant charge
Refrigerant leakage
e Drier Drier blocked with contamination
r
Suction modulating valve
Coil wire breakage
Disconnection of connector
t
Electronic expansion valve
Valve blocked with moisture
Valve blocked with contamination
Breakage of coil lead wire or disconnection of connector
Lead wire breakage or miss-mounting of evaporator inlet or outlet sensor
Electronic expansion valve malfunction
y Evaporator Abnormal frosting
Insufficient air flow rate in the evaporator
Air passage blocked by foreign material
Evaporator fan motor malfunction
Evaporator fan damage or fall out
Air short circuit around the evaporator
Reverse rotation of evaporator fan motor
C. Economizer circuit
Economizer solenoid valve
Solenoid valve coil malfunction
does not function Valve blocked with contamination
D. Defrosting is not q Manual defrost key Poor contact of connector
initiated. w
Evaporator outlet sensor
Incorrect installation of sensor
e
Defrosting solenoid valve
Valve blocked with contamination
Valve coil malfunction
r No trouble with unit Defrost interval is set to 99 H
(Demand/defrost setting)
6-2
2 Unit operates but soon stops
3 Inside temperature does not drop.
Electronic overcurrent
protection device, PT/CT
board actuation