Service manual
SiBE041134 Field Settings
Trial Operation and Field Settings 167
4. Field Settings
4.1 Model Type Setting
ARC466A6
This remote controller is common to the heat pump model and cooling only model. Use the
DIP switch on the remote controller to set the heat pump model.
Set the DIP switch to H/P as shown in the illustration. (The factory set is the heat pump
side.)
4.2 When 2 Units are Installed in 1 Room
Outline When 2 indoor units are installed in 1 room, 1 of the 2 indoor units and the corresponding
wireless remote controller can be set for different addresses.
Both the indoor unit PCB and the wireless remote controller need alteration.
Indoor Unit PCB Cut the address setting jumper JA on the control PCB.
Wireless Remote
Controller
(1) Remove the cover and take it off.
(2) Cut the address setting jumper.
H/P C/O
DIP switch
(R12275)
JA
JB
JC
ADDRESS
1
2
JA
EXIST
CUT
(R16497)
1
2
Address
Jumper
(R14631)
EXIST
CUT