Specifications
Troubleshooting SiBE04-624_B
98 Service Diagnosis
2.16 Low-voltage Detection or Over-voltage Detection
Error Code
U2
Method of Error
Detection
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Error Decision
Conditions
Low-voltage detection:
The voltage detected by the DC voltage detection circuit is below 150 V.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Over-voltage detection:
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer.
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Supposed
Causes
Supply voltage is not as specified.
Defective DC voltage detection circuit
Defective over-voltage detection circuit
Defective PAM control part
Disconnection of compressor harness
Layer short inside the fan motor winding
Defective outdoor unit PCB
Noise
Momentary fall of voltage
Momentary power failure