Service manual
Troubleshooting SiBE041102_A
86 Service Diagnosis
Troubleshooting
Correct the power supply.
Replace the outdoor 
unit PCB.
Check for such factors for a 
long term.
∗ Try to restart a few times.
(R15291)
Caution
Be sure to turn off the power switch before connecting or disconnecting 
connectors, or parts may be damaged.
NO
NO
YES
NO
YES
YES
Reconnect it.
Check the power supply voltage.
Check the connection of the 
compressor harness.
Disturbance factors
∗ Noise ∗ Power supply distortion
Repeat a few 
times.
(Precaution before turning on the power again) 
Make sure the power has been off for at 
least 30 seconds.
Replace the indoor 
unit PCB.
Turn on the 
power again. System 
restarted?
Error 
again within 3 minutes 
after turning on the 
power?
Loose or 
disconnected?
Voltage as rated?
YES
NO