Service manual
SiBE041102_A Troubleshooting
Service Diagnosis 83
4.22 Refrigerant Shortage
Remote 
Controller 
Display
U0
Method of 
Malfunction 
Detection
Refrigerant shortage detection I:
Refrigerant shortage is detected by checking the input current value and the compressor 
running frequency. If the refrigerant is short, the input current is lower than the normal value.
Refrigerant shortage detection II:
Refrigerant shortage is detected by checking the discharge pipe temperature and the opening of 
the electronic expansion valve. If the refrigerant is short, the discharge pipe temperature tends 
to rise.
Malfunction 
Decision 
Conditions
Refrigerant shortage detection I: 
The following conditions continue for 7 minutes.
Input current × input voltage 
≤
 A × output frequency + B
Output frequency > C
Refrigerant shortage detection II: 
The following conditions continue for 80 seconds.
Opening of the electronic expansion valve 
≥
 D
Discharge pipe temperature > E × target discharge pipe temperature + F
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed 
Causes
Disconnection of discharge pipe thermistor, indoor or outdoor heat exchanger thermistor, 
room or outdoor temperature thermistor
Closed stop valve
Refrigerant shortage (refrigerant leakage)
Poor compression performance of compressor
Defective electronic expansion valve
A (–)
B
 (W)
C
 (Hz)
1600/256 –160 46
D
 (pulse) E
 (–) F
 (°C)
25 class
Cooling
470
190/128 –7
Heating 211/128 –11
35 class
Cooling
470
160/128 –1.5
Heating 172/128 –8