SiEBE12-625 Troubleshooting
Service Diagnosis 201
5.3 Indoor Unit PCB Abnormality
Remote
Controller
Display
A1
Method of
Malfunction
Detection
Evaluation of zero-cross detection of power supply by indoor unit.
Malfunction
Decision
Conditions
When there is no zero-cross detection in approximately 10 continuous seconds.
Supposed
Causes
Faulty indoor unit PCB
Faulty connector connection
Troubleshooting
Note: Connector Nos. vary depending on models.
Control connector
(R1400)
YES
Connector connection check
(note).
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Replace PCBs.
Correct connections.
Is it normal?
Caution
NO
Model Type Connector No.
Wall Mounted Type 20 / 25 / 35 class Terminal strip~Control PCB
Wall Mounted Type 50 / 60 / 71 class Terminal strip~Control PCB
Duct Connected Type Terminal strip~Control PCB
Floor / Ceiling Suspended Dual Type S37
Floor Standing Type Control PCB : S7, S201, S203
Power Supply PCB : S8, S202, S204