Daikin Applied Georgia 1765 West Oak Parkway, Ste. 500 Marietta, GA 30062 Michael M Eckert, LEED AP; Sales Engineer Cell: 678.372.5034 Michael.eckert@daikinapplied.com PROJECT Georgia State University Project No 093-073-11 J – 183 Humanities – Law Building 85 Park Place Atlanta, GA 30303 MECHANICAL CONTRACTOR Gainesville Mechanical, Inc 2519 Monroe Dr Gainesville, GA 30507 770.532.9130 MECHANICAL ENGINEER Stevens & Wilkinson 100 Peachtree Street NW.
Submittal Coordination Comments: 1. Contractor to verify electrical information and communication protocol before release. (BACnet interface is currently provided) 2. CDEs are included after the Table of Contents page. Deviations or Exceptions are for either of the following: - There are indoor unit types listed in the specifications that are not scheduled or provided - There are references to branch selector boxes, which are not used (or provided) in a Heat Pump Style System.
Table of Contents – GSU Humanities Law Bldg 6SHFLILFDWLRQ &'( 959 6SHFLILFDWLRQV 959 6\VWHP 'HWDLOV ,QGRRU 8QLW 'DWD 2XWGRRU 8QLW 'DWD $FFHVVRULHV 3
SECTION 23 8129 VARIABLE REFRIGERANT VOLUME (VRV) HVAC SYSTEM REVISION #6 PART 1 GENERAL C 1.01 SECTION INCLUDES A. C C Variable refrigerant volume HVAC system includes: 1. Outdoor/Condensing unit(s). 2. Indoor/Evaporator units. 3. Branch selector units. 4. Refrigerant piping. 5. Control panels. 6. Control wiring. 1.02 RELATED REQUIREMENTS A. Section 01 7900 - Demonstration and Training. B. Section 22 1005 - Plumbing Piping: Condensate drain piping. C.
g. h. i. j. k. C 2. 3. Air Flow: Cubic feet per minute (Cubic meters per second). Fan Curves. External Static Pressure (ESP): Inches WG (Pa). Sound Pressure Level: dB(A). Electrical Data: 1) Maximum Circuit Amps (MCA). 2) Maximum Fuse Amps (MFA). 3) Maximum Starting Current (MSC). 4) Full Load Amps (FLA). 5) Total Over Current Amps (TOCA). 6) Fan Motor: HP (W). l. Weight and Dimensions. m. Maximum number of indoor units that can be served. n.
3. C C H. Project Record Documents: Record the following: 1. As-installed routing of refrigerant piping and condensate piping. 2. Locations of access panels. 3. Locations of control panels. I. Warranty: Executed warranty, made out in Owner's name. 1.05 QUALITY ASSURANCE A. Manufacturer Qualifications: 1. Company that has been manufacturing variable refrigerant volume heat pump equipment for at least 10 years. B. Installer Qualifications: Trained and approved by manufacturer of equipment. C.
3. 4. 5. 6. C Substitution requests will be considered only if required submittal data is complete; see article SUBMITTALS above. Contractor (not equipment supplier) shall certify that the use of the substitute system and equipment will not require changes to other work or re-design by Design Professional. Contractor or HVAC subcontractor shall certify that the substitute system will achieve the performance specified.
1. 2. 3. Minimum Piping Length from Outdoor/Central Unit(s) to Furthest Terminal Unit: 540 feet (165 m), actual; 620 feet (189 m), equivalent. Total Combined Liquid Line Length: 3280 feet (1000 m), minimum. Minimum Piping Length Between Indoor Units: 49 feet (15 mm). C H. Control Wiring Lengths: 1. Between Outdoor/Condenser Unit and Indoor/Evaporator Unit: 6,665 feet (2031 m), minimum. 2. Between Outdoor/Condenser Unit and Central Controller: 3,330 feet (1015 m), minimum. 3.
C 7. C 8. C B. D C C Energy Efficiency: Report EER, IEER and COP based on tests conducted at “full load” in accordance with AHRI 1230 or alternate test method approved by U.S. Department of Energy. Outdoor Units: Units and their supports designed and installed to resist wind pressures C: Supports Provided by others defined in ASCE 7. Electrical Characteristics: 1. Power - Condensing Units: 460 Volts, 3-phase, 60 Hz. 2. Power - Branch Selector Units: 208 to 230 Volts, single phase, 60 Hz. 3.
7. Power Failure Mode: Automatically restart operation after power failure without loss of programmed settings. 8. Provide refrigerant auto-charging feature and refrigerant charge check function. 9. Safety Devices: High pressure sensor and switch, low pressure sensor/switch, control circuit fuses, crankcase heaters, fusible plug, overload relay, inverter overload protector, thermal protectors for compressor and fan motors, over current protection for the inverter and anti-recycling timers. 10.
7. C C 8. C C 9. 10. C 11. C 12. 13. C D The inverter driven comprassor in each condensing unit shall be of highly efficient reluctance DC (digitally commutating), hermetically sealed scroll "02-type" with a maximum speed of 7,980 rpm. Neodymium magnets shall be adopted in the rotor construction to yield a higher torque and efficiency in the compressor instead of normal ferrite magnet type.
6. 7. C Condensate Drainage: Built-in condensate drain pan with PVC drain connection. Cabinet Insulation: Sound absorbing foamed polystyrene and polyethylene insulation. B. Recessed Ceiling Units - 3 FT by 3 FT: Four-way airflow cassette with central return air grille, for installation in a fixed ceiling. 1. Face Size: 33 inches (939 mm) square, nominal. 2. Cabinet Height: Maximum of 10 inches (250 mm) above face of ceiling. 3. Exposed Housing: White, impact resistant, with washable decoration panel. 4.
C F. Wall Surface-Mounted Units: Finished white casing, with removable front grille; foamed polystyrene and polyethylene sound insulation; wall mounting plate; polystyrene condensate drain pan. 1. Airflow Control: Auto-swing louver that closes automatically when unit stops; five (5) steps of discharge angle, set using remote controller; upon restart, discharge angle defaulting to same angle as previous operation. 2. Sound Pressure Range: Measured at low speed at 3.
B. Prepare and start equipment and system in accordance with manufacturer's instructions and recommendations. C. Adjust equipment for proper operation within manufacturer's published tolerances. D. Start-up system reports shall be included in closeout documents. E. Four hours of Service Checker Data shall be recorded in accordance to manufacturer recommendations to insure proper installation. 3.05 PRESSURE TESTING AND VACUUMING REFRIGERANT PIPING A.
Daikin Applied Georgia 1765 West Oak Parkway, Ste. 500 Marietta, GA 30062 Michael M Eckert, LEED AP; Sales Engineer Cell: 678.372.5034 Michael.eckert@daikinapplied.
Section 238129 Daikin AC Model Number: RXYQ72PBYD RXYQ96PBYD RXYQ120PBYD RXYQ144PBYD (2x RXYQ72PBYD) Part 1 – GENERAL VARIABLE REFRIGERANT VOLUME (VRVIII) AIR CONDITIONING SPECIFICATION – Heat Pump 1.01 SYSTEM DESCRIPTION The variable capacity, heat pump air conditioning system will be a Daikin Variable Refrigerant Volume Series (heat or cool model) split system as specified.
1.02 VRVIII FEATURES AND BENEFITS A. Voltage Platform – Heat pump condensing units will be available with a 460V/3/60 power supply. B. Advanced Zoning – A single system will provide for up to 62 zones. C. Autocharging – Each system will have a refrigerant auto-charging function. D. Oil Return Heating – Each system will maintain continuous heating during oil return operation.
O. Low Sound Levels – Each system will use indoor and condensing units with quiet operation as low as 27 dB(A). 1.03 QUALITY ASSURANCE A. The units will be tested by a Nationally Recognized Testing Laboratory (NRTL), in accordance with ANSI/UL 1995 – Heating and Cooling Equipment and bear the Listed Mark. B. All wiring will be in accordance with the National Electric Code (NEC). C.
The mechanical contractor’s installation price will be based on the systems installation requirements. The mechanical contractor bids with complete knowledge of the HVAC system requirements. Part 3 – PERFORMANCE 3.01 The VRVIII RXYQ system will perform as indicated below. Model Number System IEER* (part load - ducted) System IEER* (part load – non-ducted) System IEER* (part load - mixed) RXYQ72PBYD RXYQ96PBYD RXYQ120PBYD RXYQ144PBYD 21.5 18.8 17.2 22.1 25.8 23.0 20.4 21.5 23.7 20.9 18.8 21.
The operating range in heating will be 0°F DB – 77°F DB / -4°F WB – 60°F WB. Cooling mode indoor room temperature range will be 57°F-77°F WB. Heating mode indoor room temperature range will be 59°F-80°F DB. 3.
fan motors, over current protection for the inverter and antirecycling timers. 10. To ensure the liquid refrigerant does not flash when supplying to the various indoor units, the circuit will be provided with a subcooling feature. 11. Oil recovery cycle will be automatic occurring 2 hours after start of operation and then every 8 hours of operation. Each system will maintain continuous heating during oil return operation.
7. Night setback control of the fan motor for low noise operation by way of automatically limiting the maximum speed will be a standard feature. Operation sound level will be selectable from 3 steps as shown below. D. Condenser Coil: 1. The condenser coil will be manufactured from copper tubes expanded into aluminum fins to form a mechanical bond. 2. The heat exchanger coil will be of a waffle louver fin and rifled bore tube design to ensure high efficiency performance. 3.
a minimum of 6 compressors. In the event of compressor failure the remaining compressors will continue to operate and provide heating or cooling as required at a proportionally reduced capacity. The microprocessor and associated controls will be designed to specifically address this condition. Tonnage Number of Compressors 1 2 2 4 6 8 9 12 Compressor Types 1 inverter 1 inverter + 1 fixed 1 inverter + 1 fixed (1 inverter) x 2 10.
FXFQ INDOOR UNIT – ROUND FLOW CEILING CASSETTE UNIT (3’x3’) FXZQ INDOOR UNIT – 4 WAY CEILING CASSETTE UNIT (2’x2’) FXMQ_M INDOOR UNIT – CONCEALED CEILING DUCTED UNIT (Med. Static) FXMQ_P INDOOR UNIT – CONCEALED CEILING DUCTED UNIT (Med.
temperature when used with Daikin remote control BRC1E72 and BRC2A71. The indoor units sound pressure will range from 27 dB(A) to 34 dB(A) at low speed measured at 5 feet below the unit. B. Performance: Each unit’s performance is based on nominal operating conditions: C. Indoor Unit: 1. The Daikin indoor unit FXFQ will be completely factory assembled and tested.
E. F. G. H. I. 4.07 6. The cabinet will be constructed with sound absorbing foamed polystyrene and polyethylene insulation. 7. Optional high efficiency MERV 13 air filters are available for each model unit. Fan: 1. The fan will be direct-drive turbo fan type with statically and dynamically balanced impeller with three fan speeds available. 2. The fan motor will operate on 208/230 volts, 1 phase, 60 hertz with a motor output range from 0.08 to 0.16 HP. 3.
A. General: Daikin indoor unit FXAQ will be a wall mounted fan coil unit, operable with refrigerant R-410A, equipped with an electronic expansion valve, for installation onto a wall within a conditioned space. This compact design with finished white casing will be available in capacities from 7,500 Btu/h to 24,000 Btu/h. Model numbers are FXAQ07PVJU, FXAQ09PVJU, FXAQ12PVJU, FXAQ18PVJU and FXAQ24PVJU to be connected to outdoor unit model RXYQ / RXYMQ / RWEYQ heat pump and REYQ / RWEYQ heat recovery model.
4. 5. 6. 7. D. E. F. G. H. Return air will be through a resin net mold resistant filter. The indoor units will be equipped with a condensate pan. The indoor units will be equipped with a return air thermistor. The indoor unit will be separately powered with 208~230V/1phase/60Hz. 8. The voltage range will be 253 volts maximum and 187 volts minimum. Unit Cabinet: 1. The cabinet will be affixed to a factory supplied wall mounting template and located in the conditioned space. 2.
Daikin Applied Georgia 1765 West Oak Parkway, Ste. 500 Marietta, GA 30062 Michael M Eckert, LEED AP; Sales Engineer Cell: 678.372.5034 Michael.eckert@daikinapplied.com VRV SYSTEM DETAILS Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC Piping Bse Refr % °F BTU/h BTU/h °F BTU/h BTU/h ft lbs HP-01 RXYQ144PBYD 92 96.0 120658 111563BTU/h 47.0 / 39.4 161994 145995BTU/h 147.6 33.0 HP-02 RXYQ96PBYD 88 96.0 80161 70993BTU/h 47.0 / 39.4 107996 92997BTU/h 147.6 21.
Produced on 12/23/2013 with Xpress Selection V6.5.3 - database Central_USA 9.1.5 Project name Reference Client name Revision J-183 Hunmanities - Law Bldg GSU S&W 1 Selection parameters of the indoor units can be found under the chapter Indoor unit details Selection parameters of the outdoor units can be found under the chapter Outdoor unit details Only the data published in the data book are correct. This program uses close approximations of these data. 1.
2. Indoor Unit Details 2.1. Table of Abbreviations Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Suct Disch Airflow Sound PS MCA Fuses WxHxD Wght Logical name of the device Device model name Indoor conditions in cooling (dry bulb temp. / wet bulb temp.
2.2. HP-01 - RXYQ144PBYD Actual capacity data at conditions and connection ratio (92%) as entered Name IU-103 IU-199 IU-198 IU-099 IU-098 FCU Tmp C °F FXFQ36PVJU FXAQ24PVJU FXAQ24PVJU FXAQ24PVJU FXAQ24PVJU Rq TC BTU/h 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 TC BTU/h 6824 6824 6824 6824 6824 Rq SC BTU/h 30424 20285 20285 20285 20285 6824 6824 6824 6824 6824 SC BTU/h 24677 15351 15351 15351 15351 Tmp H °F 70.0 70.0 70.0 70.0 70.
2.3. HP-02 - RXYQ96PBYD Actual capacity data at conditions and connection ratio (88%) as entered Name IU-399 IU-398 IU-299 IU-298 FCU Tmp C °F FXAQ24PVJU FXAQ24PVJU FXAQ12PVJU FXAQ24PVJU Rq TC BTU/h 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 TC BTU/h 6824 6824 6824 6824 Rq SC BTU/h 20285 20285 10139 20285 6824 6824 6824 6824 SC BTU/h 15351 15351 7814 15351 Tmp H °F 70.0 70.0 70.0 70.
2.4. HP-03 - RXYQ120PBYD Actual capacity data at conditions and connection ratio (100%) as entered Name IU-699 IU-698 IU-599 IU-598 IU-499 IU-498 FCU Tmp C °F FXAQ12PVJU FXAQ24PVJU FXAQ12PVJU FXAQ24PVJU FXAQ24PVJU FXAQ24PVJU Rq TC BTU/h 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 TC BTU/h 6824 6824 6824 6824 6824 6824 Rq SC BTU/h 10139 20285 10139 20285 20285 20285 6824 6824 6824 6824 6824 6824 SC BTU/h 7814 15351 7814 15351 15351 15351 Tmp H °F 70.0 70.0 70.0 70.
2.5. HP-04 - RXYQ144PBYD Actual capacity data at conditions and connection ratio (100%) as entered Name IU-044 IU-093 IU-034A IU-034B FCU Tmp C °F FXFQ48PVJU FXAQ24PVJU FXAQ24PVJU FXFQ48PVJU Rq TC BTU/h 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 TC BTU/h 6824 6824 6824 6824 Rq SC BTU/h 40563 20285 20285 40563 SC BTU/h 6824 6824 6824 6824 30563 15351 15351 30563 Tmp H °F 70.0 70.0 70.0 70.
2.6. HP-05 - RXYQ144PBYD Actual capacity data at conditions and connection ratio (92%) as entered Name IU-393 IU-394 IU-293 IU-294 IU-193 IU-142 FCU Tmp C °F FXAQ24PVJU FXAQ24PVJU FXAQ12PVJU FXAQ24PVJU FXAQ24PVJU FXAQ24PVJU Rq TC BTU/h 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 TC BTU/h 6824 6824 6824 6824 6824 6824 Rq SC BTU/h 20285 20285 10139 20285 20285 20285 6824 6824 6824 6824 6824 6824 SC BTU/h 15351 15351 7814 15351 15351 15351 Tmp H °F 70.0 70.0 70.0 70.
2.7. HP-06 - RXYQ72PBYD Actual capacity data at conditions and connection ratio (100%) as entered Name IU-791 IU-622 IU-593 IU-493 FCU Tmp C °F FXAQ24PVJU FXAQ12PVJU FXAQ24PVJU FXAQ12PVJU Rq TC BTU/h 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 TC BTU/h 6824 6824 6824 6824 Rq SC BTU/h 20285 10139 20285 10139 6824 6824 6824 6824 SC BTU/h 15351 7814 15351 7814 Tmp H °F 70.0 70.0 70.0 70.
2.8. HP-07 - RXYQ144PBYD Actual capacity data at conditions and connection ratio (92%) as entered Name IU-793b IU-793 IU-701 IU-631 IU-630 FCU Tmp C °F FXAQ24PVJU FXAQ24PVJU FXFQ12PVJU FXFQ36PVJU FXFQ36PVJU Rq TC BTU/h 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 75.2 / 62.6 TC BTU/h 6824 6824 6824 6824 6824 Rq SC BTU/h 20285 20285 10139 30424 30424 SC BTU/h 6824 6824 6824 6824 6824 15351 15351 9052 24677 24677 Tmp H °F 70.0 70.0 70.0 70.0 70.
3. Outdoor Unit Details 3.1. Table of Abbreviations Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC Piping Bse Refr Ex Refr PS MCA MFA Run Amps St Curr Fuses WxHxD Wght EER IEER COP 47°F COP 17°F Logical name of the device Device model name Connection ratio Outdoor temperature in cooling Available cooling capacity Required cooling capacity Outdoor conditions in heating (dry bulb temp. / wet bulb temp.
3.2. Outdoor Details Name HP-01 HP-02 HP-03 HP-04 HP-05 HP-06 HP-07 Name HP-01 HP-02 HP-03 HP-04 HP-05 HP-06 HP-07 Model RXYQ144PBYD RXYQ96PBYD RXYQ120PBYD RXYQ144PBYD RXYQ144PBYD RXYQ72PBYD RXYQ144PBYD Model RXYQ144PBYD * RXYQ72PBYD * RXYQ72PBYD RXYQ96PBYD RXYQ120PBYD RXYQ144PBYD * RXYQ72PBYD * RXYQ72PBYD RXYQ144PBYD * RXYQ72PBYD * RXYQ72PBYD RXYQ72PBYD RXYQ144PBYD * RXYQ72PBYD * RXYQ72PBYD Comb % Tmp C °F CC BTU/h 92 88 100 100 92 100 92 96.0 96.0 96.0 96.0 96.0 96.0 96.
3.2.1.
3.2.2. HP-02 - RXYQ96PBYD Model RXYQ96PBYD FXAQ12PVJU FXAQ24PVJU KHRP26A22T KHRP26A33T BRC1E72 Qty 1 1 3 2 1 4 Description Heat pump VRV P(B) R410A (460V) VRV A (P) - Wall Mounted Unit VRV A (P) - Wall Mounted Unit REFNET branch piping kit REFNET branch piping kit Navigation Remote Controller 2013 The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
3.2.3. HP-03 - RXYQ120PBYD Model RXYQ120PBYD FXAQ12PVJU FXAQ24PVJU KHRP26A22T KHRP26A33T KHRP26M72TU BRC1E72 Qty 1 2 4 1 3 1 6 Description Heat pump VRV P(B) R410A (460V) VRV A (P) - Wall Mounted Unit VRV A (P) - Wall Mounted Unit REFNET branch piping kit REFNET branch piping kit REFNET branch piping kit Navigation Remote Controller 2013 The Xpress Selection Program is property of Daikin Europe NV.
3.2.4. HP-04 - RXYQ144PBYD Model RXYQ144PBYD FXAQ24PVJU FXFQ48PVJU KHRP26A33T KHRP26M72TU BRC1E72 BYCP125K-W1 BHFP22P100U Piping 3/8" Piping 1/2" Piping 5/8" Piping 7/8" Piping 1 1/8" Qty 1 2 2 2 1 4 2 1 189.0ft 100.0ft 159.0ft 30.0ft 100.
3.2.5. HP-05 - RXYQ144PBYD Model RXYQ144PBYD FXAQ12PVJU FXAQ24PVJU KHRP26A22T KHRP26A33T KHRP26M72TU BRC1E72 BHFP22P100U Qty 1 1 5 1 3 1 6 1 Description Heat pump VRV P(B) R410A (460V) VRV A (P) - Wall Mounted Unit VRV A (P) - Wall Mounted Unit REFNET branch piping kit REFNET branch piping kit REFNET branch piping kit Navigation Remote Controller 2013 Outdoor Multi Connection Pipe Kit - VRV P Series HP The Xpress Selection Program is property of Daikin Europe NV.
3.2.6. HP-06 - RXYQ72PBYD Model RXYQ72PBYD FXAQ12PVJU FXAQ24PVJU KHRP26A22T KHRP26A33T BRC1E72 Qty 1 2 2 2 1 4 Description Heat pump VRV P(B) R410A (460V) VRV A (P) - Wall Mounted Unit VRV A (P) - Wall Mounted Unit REFNET branch piping kit REFNET branch piping kit Navigation Remote Controller 2013 The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
3.2.7.
4. Piping Diagrams Pipes marked with * in the diagrams must be connected to the device with a reducing joint. 4.1. Piping HP-01 HP-01 RXYQ144PBYD RXYQ72PBYD RXYQ72PBYD 3/8"x3/4" 3/8"x3/4" BHFP22P100U 1/2"x1 1/8" 3/8"x5/8" KHRP26M72TU IU-103 FXFQ36PVJU 3/8"x7/8" 3/8"x5/8" KHRP26A33T IU-199 FXAQ24PVJU 3/8"x7/8" 3/8"x5/8" KHRP26A33T IU-198 FXAQ24PVJU 3/8"x5/8" 3/8"x5/8" KHRP26A22T IU-099 FXAQ24PVJU 3/8"x5/8" IU-098 FXAQ24PVJU Warning: The pipe diameter values are purely indicative.
4.2. Piping HP-02 HP-02 RXYQ96PBYD 3/8"x7/8" 3/8"x5/8" KHRP26A33T IU-399 FXAQ24PVJU 3/8"x3/4" 3/8"x5/8" KHRP26A22T IU-398 FXAQ24PVJU 3/8"x5/8" 1/4"x1/2" KHRP26A22T IU-299 FXAQ12PVJU 3/8"x5/8" IU-298 FXAQ24PVJU Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter might be required. The Xpress Selection Program is property of Daikin Europe NV.
4.3. Piping HP-03 HP-03 RXYQ120PBYD 1/2"x1 1/8" 1/4"x1/2" KHRP26M72TU IU-699 FXAQ12PVJU 3/8"x7/8" 3/8"x5/8" KHRP26A33T IU-698 FXAQ24PVJU 3/8"x7/8" 1/4"x1/2" KHRP26A33T IU-599 FXAQ12PVJU 3/8"x7/8" 3/8"x5/8" KHRP26A33T IU-598 FXAQ24PVJU 3/8"x5/8" 3/8"x5/8" KHRP26A22T IU-499 FXAQ24PVJU 3/8"x5/8" IU-498 FXAQ24PVJU Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter might be required.
4.4. Piping HP-04 HP-04 RXYQ144PBYD RXYQ72PBYD RXYQ72PBYD 3/8"x3/4" 3/8"x3/4" BHFP22P100U 100.0ft 1/2"x1 1/8" 114.0ft [1] 3/8"x5/8" KHRP26M72TU 10.0ft 3/8"x7/8" 20.0ft 3/8"x5/8" KHRP26A33T IU-044 FXFQ48PVJU IU-093 FXAQ24PVJU 20.0ft 3/8"x7/8" 10.0ft 3/8"x5/8" KHRP26A33T IU-034A FXAQ24PVJU 15.0ft 3/8"x5/8" IU-034B FXFQ48PVJU The Xpress Selection Program is property of Daikin Europe NV.
4.5. Piping HP-05 HP-05 RXYQ144PBYD RXYQ72PBYD RXYQ72PBYD 3/8"x3/4" 3/8"x3/4" BHFP22P100U 1/2"x1 1/8" 3/8"x5/8" KHRP26M72TU IU-393 FXAQ24PVJU 3/8"x7/8" 3/8"x5/8" KHRP26A33T IU-394 FXAQ24PVJU 3/8"x7/8" 1/4"x1/2" KHRP26A33T IU-293 FXAQ12PVJU 3/8"x7/8" 3/8"x5/8" KHRP26A33T IU-294 FXAQ24PVJU 3/8"x5/8" 3/8"x5/8" KHRP26A22T IU-193 FXAQ24PVJU 3/8"x5/8" IU-142 FXAQ24PVJU Warning: The pipe diameter values are purely indicative.
4.6. Piping HP-06 HP-06 RXYQ72PBYD 3/8"x3/4" 3/8"x5/8" KHRP26A33T IU-791 FXAQ24PVJU 3/8"x5/8" 1/4"x1/2" KHRP26A22T IU-622 FXAQ12PVJU 3/8"x5/8" 3/8"x5/8" KHRP26A22T IU-593 FXAQ24PVJU 1/4"x1/2" IU-493 FXAQ12PVJU Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter might be required. The Xpress Selection Program is property of Daikin Europe NV.
4.7. Piping HP-07 HP-07 RXYQ144PBYD RXYQ72PBYD RXYQ72PBYD 3/8"x3/4" 3/8"x3/4" BHFP22P100U 1/2"x1 1/8" 3/8"x5/8" KHRP26M72TU IU-793b FXAQ24PVJU 3/8"x7/8" 3/8"x5/8" KHRP26A33T IU-793 FXAQ24PVJU 3/8"x7/8" 1/4"x1/2" KHRP26A33T IU-701 FXFQ12PVJU 3/8"x7/8" 3/8"x5/8" KHRP26A33T IU-631 FXFQ36PVJU 3/8"x5/8" IU-630 FXFQ36PVJU Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a different pipe diameter might be required.
5. Wiring Diagrams P1P2 = Please select the cable type and size in accordance with the databook. F1F2 = Please select the cable type and size in accordance with the databook. 5.1. Wiring HP-01 to centralized controller IU-103 FXFQ36PVJU HP-01 RXYQ144PBYD OUT F1,F2 IN F1,F2 P1,P2 L1, L2 F1,F2 BRC1E72 3.8A 1ph 1.4A 1ph RXYQ72PBYD L1, L2, L3 Q1,Q2 IU-199 FXAQ24PVJU 16A 3ph L1, L2 F1,F2 RXYQ72PBYD Q1,Q2 P1,P2 BRC1E72 0.
5.2. Wiring HP-02 to centralized controller HP-02 RXYQ96PBYD IU-399 FXAQ24PVJU IN F1,F2 OUT F1,F2 L1, L2, L3 F1,F2 P1,P2 L1, L2 BRC1E72 2.2A 1ph 0.6A 1ph 21A 3ph IU-398 FXAQ24PVJU F1,F2 L1, L2 IU-299 FXAQ12PVJU F1,F2 BRC1E72 0.6A 1ph P1,P2 L1, L2 IU-298 FXAQ24PVJU F1,F2 P1,P2 BRC1E72 0.4A 1ph P1,P2 L1, L2 BRC1E72 0.6A 1ph The Xpress Selection Program is property of Daikin Europe NV.
5.3. Wiring HP-03 to centralized controller HP-03 RXYQ120PBYD IU-699 FXAQ12PVJU IN F1,F2 OUT F1,F2 L1, L2, L3 F1,F2 P1,P2 L1, L2 BRC1E72 3.2A 1ph 0.4A 1ph 21A 3ph IU-698 FXAQ24PVJU F1,F2 L1, L2 IU-599 FXAQ12PVJU F1,F2 F1,F2 F1,F2 BRC1E72 0.4A 1ph BRC1E72 0.6A 1ph P1,P2 L1, L2 IU-498 FXAQ24PVJU 0.6A 1ph P1,P2 L1, L2 IU-499 FXAQ24PVJU BRC1E72 P1,P2 L1, L2 IU-598 FXAQ24PVJU F1,F2 P1,P2 BRC1E72 0.6A 1ph P1,P2 L1, L2 BRC1E72 0.
5.4. Wiring HP-04 to centralized controller HP-04 RXYQ144PBYD IU-044 FXFQ48PVJU IN F1,F2 OUT F1,F2 F1,F2 P1,P2 L1, L2 BRC1E72 4.2A 1ph 1.5A 1ph RXYQ72PBYD Q1,Q2 L1, L2, L3 IU-093 FXAQ24PVJU 16A 3ph RXYQ72PBYD Q1,Q2 P1,P2 L1, L2 F1,F2 BRC1E72 0.6A 1ph L1, L2, L3 16A 3ph IU-034A FXAQ24PVJU L1, L2 F1,F2 IU-034B FXFQ48PVJU F1,F2 P1,P2 BRC1E72 0.6A 1ph P1,P2 L1, L2 BRC1E72 1.5A 1ph The Xpress Selection Program is property of Daikin Europe NV.
5.5. Wiring HP-05 to centralized controller HP-05 RXYQ144PBYD IU-393 FXAQ24PVJU IN F1,F2 OUT F1,F2 F1,F2 P1,P2 L1, L2 BRC1E72 3.4A 1ph 0.6A 1ph RXYQ72PBYD Q1,Q2 L1, L2, L3 IU-394 FXAQ24PVJU 16A 3ph RXYQ72PBYD Q1,Q2 F1,F2 P1,P2 L1, L2 BRC1E72 0.6A 1ph L1, L2, L3 16A 3ph IU-293 FXAQ12PVJU F1,F2 L1, L2 IU-294 FXAQ24PVJU F1,F2 F1,F2 0.4A 1ph BRC1E72 0.6A 1ph P1,P2 L1, L2 IU-142 FXAQ24PVJU BRC1E72 P1,P2 L1, L2 IU-193 FXAQ24PVJU F1,F2 P1,P2 BRC1E72 0.
5.6. Wiring HP-06 to centralized controller HP-06 RXYQ72PBYD IU-791 FXAQ24PVJU IN F1,F2 OUT F1,F2 L1, L2, L3 F1,F2 P1,P2 L1, L2 BRC1E72 2A 1ph 0.6A 1ph 16A 3ph IU-622 FXAQ12PVJU F1,F2 L1, L2 IU-593 FXAQ24PVJU F1,F2 BRC1E72 0.4A 1ph P1,P2 L1, L2 IU-493 FXAQ12PVJU F1,F2 P1,P2 BRC1E72 0.6A 1ph P1,P2 L1, L2 BRC1E72 0.4A 1ph The Xpress Selection Program is property of Daikin Europe NV.
5.7. Wiring HP-07 to centralized controller IU-793b FXAQ24PVJU HP-07 RXYQ144PBYD OUT F1,F2 IN F1,F2 P1,P2 L1, L2 F1,F2 BRC1E72 4.3A 1ph 0.6A 1ph RXYQ72PBYD Q1,Q2 L1, L2, L3 IU-793 FXAQ24PVJU 16A 3ph RXYQ72PBYD Q1,Q2 P1,P2 L1, L2 F1,F2 BRC1E72 0.6A 1ph L1, L2, L3 16A 3ph IU-701 FXFQ12PVJU L1, L2 F1,F2 IU-631 FXFQ36PVJU IU-630 FXFQ36PVJU BRC1E72 0.3A 1ph P1,P2 L1, L2 F1,F2 F1,F2 P1,P2 BRC1E72 1.4A 1ph P1,P2 L1, L2 BRC1E72 1.
6. Centralized Controllers 6.1. Concept Global Controller Models BACnet Interface # controllers 1 Control Groups Control group 1 HP-03 (6) # outdoors 7 HP-05 (6) # indoors 34 HP-01 (5) HP-07 (5) HP-02 (4) HP-04 (4) HP-06 (4) The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
6.2. Control group 1 BACnet Interface DMS502B71 1 HP-03 (6) RXYQ120PBYD 2 OUT F1,F2 HP-05 (6) RXYQ144PBYD HP-01 (5) RXYQ144PBYD HP-07 (5) RXYQ144PBYD HP-02 (4) RXYQ96PBYD HP-04 (4) RXYQ144PBYD HP-06 (4) RXYQ72PBYD The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
6.3. Dimensional Drawings BACnet Interface DMS502B71 The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection Program.
Daikin Applied Georgia 1765 West Oak Parkway, Ste. 500 Marietta, GA 30062 Michael M Eckert, LEED AP; Sales Engineer Cell: 678.372.5034 Michael.eckert@daikinapplied.
Specifications EDUS391100-F6 1. Specifications Wall Mounted Type Model FXAQ07PVJU FXAQ09PVJU Power Supply FXAQ12PVJU 1 phase, 208/230V, 60Hz +1, +3 Cooling Capacity Btu/h 7,500 9,500 12,000 +2, +3 Heating Capacity Btu/h 8,500 10,500 13,500 White (3.0Y8.5/0.5) White (3.0Y8.5/0.5) White (3.0Y8.5/0.5) in (mm) 11–3/8 × 31–1/4 × 9–1/4 (289 x 794 x 235) 11–3/8 × 31–1/4 × 9–1/4 (289 x 794 x 235) 11–3/8 × 31–1/4 × 9–1/4 (289 x 794 x 235) 2×14×17 2×14×17 2×14×17 1.73 1.73 1.
EDUS391100-F6 Specifications Wall Mounted Type Model FXAQ18PVJU Power Supply FXAQ24PVJU 1 phase, 208/230V, 60Hz +1, +3 Cooling Capacity Btu/h 18,000 24,000 +2, +3 Heating Capacity Btu/h 20,000 26,500 White (3.0Y8.5/0.5) White (3.0Y8.5/0.5) in (mm) 11–3/8 × 41–3/8 × 9–1/4 (289 x 1051 x 235) 11–3/8 × 41–3/8 × 9–1/4 (289 x 1051 x 235) 2×14×17 2×14×17 ft² (m²) 2.29 (0.7) 2.29 (0.
Dimensions EDUS391100-F6 2. Dimensions FXAQ07PVJU/FXAQ09PVJU/FXAQ12PVJU 3D075388A Unit (in.
Dimensions EDUS391100-F6 FXAQ24PVJU 3D075390A Unit (in.
Wiring Diagrams EDUS391100-F6 4.
EDUS391100-F6 Electric Characteristics 5. Electric Characteristics 4D075550 6.
Capacity Tables EDUS391100-F6 7. Capacity Tables 7.1 Cooling Capacity FXAQ-P Outdoor Unit size air temp. 07 09 12 18 24 °FDB 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 [Cooling capacity] 61 °FWB TC SHC MBh MBh 5.9 5.6 5.9 5.6 5.9 5.6 5.9 5.6 5.9 5.6 5.9 5.6 5.9 5.6 5.9 5.6 7.5 6.5 7.5 6.5 7.5 6.5 7.5 6.5 7.5 6.5 7.5 6.5 7.5 6.5 7.5 6.5 9.5 7.9 9.5 7.9 9.5 7.9 9.5 7.9 9.5 7.9 9.5 7.9 9.5 7.9 9.5 7.9 14.2 11.7 14.
EDUS391100-F6 7.2 Capacity Tables Heating Capacity FXAQ-P Unit size 07 09 12 18 24 [Heating capacity] Outdoor air temp. °FDB 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 47.0 51.0 54.0 57.0 60.0 °FWB 20.0 24.0 28.0 32.0 36.0 40.0 43.0 47.0 50.0 53.0 56.0 20.0 24.0 28.0 32.0 36.0 40.0 43.0 47.
Specifications EDUS391000-F1 1. Specifications Ceiling Mounted Cassette Type (Round Flow) Model FXFQ09PVJU FXFQ12PVJU FXFQ18PVJU FXFQ24PVJU 1+, 3+ Cooling Capacity Btu/h 9,500 12,000 18,000 24,000 2+, 3+ Heating Capacity Btu/h 10,500 13,500 20,000 27,000 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate in.
EDUS391000-F1 Specifications Ceiling Mounted Cassette Type (Round Flow) FXFQ30PVJU FXFQ36PVJU FXFQ48PVJU 1+, 3+ Cooling Capacity Model Btu/h 30,000 36,000 48,000 2+, 3+ Heating Capacity Btu/h 34,000 40,000 54,000 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate in. (mm) 9-11/16 × 33-1/16 × 33-1/16 (246 x 840 x 840) 11-5/16×33-1/16×33-1/16 (287 x 840 x 840) 11-5/16×33-1/16×33-1/16 (287 x 840 x 840) 2×10×21 2×12×21 2×12×21 ft² (m2) 4.80 (1.46) 5.76 (1.8) 5.
DO NOT PLACE THE UNIT IN AREAS WITH EXCESSIVE HUMIDITY. WHEN HUMIDITY EXCEEDS 80%, CONDENSATION CAN FORM ON THE UNIT. 3D070522 Dimensions 4 EDUS391000-F1 2. Dimensions FXFQ09PVJU FXFQ12PVJU FXFQ18PVJU Unit (in.
DO NOT PLACE THE UNIT IN AREAS WITH EXCESSIVE HUMIDITY. WHEN HUMIDITY EXCEEDS 80%, CONDENSATION CAN FORM ON THE UNIT. 3D070523 Dimensions 6 EDUS391000-F1 FXFQ36PVJU FXFQ48PVJU Unit (in.
Wiring Diagrams EDUS391000-F1 4.
EDUS391000-F1 Electric Characteristics 5.
Capacity Tables EDUS391000-F1 6. Capacity Tables 6.1 Cooling Capacity FXFQ-P Indoor Unit [Cooling Capacity] Outdoor Air Temp. °FDB 09 12 18 24 30 36 48 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 75 79 83 87 91 95 99 103 61 TC MBh 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 14.2 14.2 14.2 14.2 14.2 14.2 14.2 14.2 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 23.7 23.7 23.
EDUS391000-F1 6.2 Capacity Tables Heating Capacity FXFQ-P Indoor Unit [Heating Capacity] Outdoor Air Temp. °FDB 22.0 26.0 30.0 35.0 39.0 44.0 09 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 12 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 18 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 24 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 30 44.0 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 36 47.0 51.0 54.0 57.0 60.0 22.0 26.0 30.0 35.0 39.0 44.0 48 47.0 51.0 54.
Daikin Applied Georgia 1765 West Oak Parkway, Ste. 500 Marietta, GA 30062 Michael M Eckert, LEED AP; Sales Engineer Cell: 678.372.5034 Michael.eckert@daikinapplied.
Specifications EDUS391005-R1 1. Specifications Model Name RXYQ72PBYD RXYQ96PBYD RXYQ120PBYD Power Supply 3 phase, 460V, 60Hz 3 phase, 460V, 60Hz 3 phase, 460V, 60Hz 72,000 96,000 120,000 69,000 92,000 114,000 81,000 108,000 135,000 77,000 103,000 129,000 Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.
EDUS391005-R1 Specifications Model Name (Combination Unit) RXYQ144PBYD RXYQ168PBYD RXYQ192PBYD Model Name (Independent Unit) RXYQ72PBYD RXYQ72PBYD RXYQ72PBYD RXYQ96PBYD RXYQ72PBYD RXYQ120PBYD 3 phase, 460V, 60Hz 3 phase, 460V, 60Hz 3 phase, 460V, 60Hz 144,000 168,000 192,000 138,000 160,000 184,000 162,000 188,000 216,000 Power Supply +1 Cooling Capacity Nominal +2 Heating Capacity Nominal Rated Rated Btu / h Btu / h Casing Color Dimensions: (H×W×D) in.
EDUS391005-R1 Dimensions 2.
Dimensions EDUS391005-R1 C: 3D070518A RXYQ96PBYD / RXYQ120PBYD 8 86 RXYQ-PBYD Heat Pump (460V)
RXYQ-PBYD Heat Pump (460V) 87 from Section 3. units person NOTE: If more units are to be installed than are shown in Section 3, your layout should take account of the possibility of short circuiting.
Service Space EDUS391005-R1 3. Service Space NOTE: If more units are to be installed than are shown in Section 3, your layout should take account of the possibility of short circuiting.
EDUS391005-R1 Wiring Diagrams 5.
Wiring Diagrams EDUS391005-R1 GROUND GROUND 3D070563C RXYQ96PBYD / RXYQ120PBYD 18 90 RXYQ-PBYD Heat Pump (460V)
RXYQ-PBYD Heat Pump (460V) FUSE / BREAKER FUSE / BREAKER FUSE / BREAKER Wiring should comply with applicable local and national codes. 9) FUSE / BREAKER lost C: 3D058621D 7) Be sure to install the switch and the breaker/fuse to the power line of each piece of equipment. 8) FUSE / BREAKER ground 4) Field wiring diagram is to be used as a guideline only. 5) 6) EDUS391005-R1 Field Wiring 6.
20 92 FUSE / BREAKER FUSE / BREAKER FUSE / BREAKER 4) Field wiring diagram is to be used as a guideline only. ground Wiring should comply with applicable local and national codes. FUSE / BREAKER 9) FUSE / BREAKER FUSE / BREAKER lost 7) Be sure to install the switch and the breaker/fuse to the power line of each piece of equipment.
Electric Characteristics EDUS391005-R1 7. Electric Characteristics MOP RXYQ72PBYD 16 20 RXYQ96PBYD 21 25 65 RXYQ120PBYD 21 25 65 0.75 -- 0.6 0.35 x 2 0.5 x 2 5.4 + 8.4 0.35 x2 0.5 x 2 1. MOP :Maximum Overcurrent Protection (A) 2. 3. 4. 5. 6.
EDUS391005-R1 Electric Characteristics MCA MOP 0.75+ 0.75 +0.75 0.75 60 460 416 508 16 20.216+ +20.2 20+20 25 + 25 -- RXYQ168PBYD RXQY72PBYD RXYQ96PBYD 60 460 416 508 20.216 + 20.3 + 21 2520+25 + 25 69 7.1 +3.9 + 8.4 0.75 +(0.35x2) 0.75 + 0.75 0.6+(0.5x2) RXYQ192PBYD RXYQ72PBYD RXYQ120PBYD 60 460 416 508 21 20.316+ +20.3 2520+25 + 25 69 7.1 + 5.4 + 8.4 0.75+(0.35x2) 0.75 + 0.75 0.6+(0.5x2) 0.8 + 0.
EDUS391005-R1 Capacity Tables (Reference Data) 8. Capacity Tables (Reference Data) 8.1 Cooling Capacity (RXYQ-PBYD) These tables are based on projection. Actual results may vary according to conditions of use. RXYQ72PBYD Combi- Outdoor nation air temp.
Capacity Tables (Reference Data) EDUS391005-R1 RXYQ96PBYD Combi- Outdoor nation air temp. % 130 120 110 100 °FDB 23 30 40 50 54 58 62 66 70 72 75 79 83 87 91 93 95 99 103 106 110 115 118 122 23 30 40 50 54 58 62 66 70 72 75 79 83 87 91 93 95 99 103 106 110 115 118 122 23 30 40 50 54 58 62 66 70 72 75 79 83 87 91 93 95 99 103 106 110 115 118 122 23 30 40 50 54 58 62 66 70 72 75 79 83 87 91 93 95 99 103 106 110 115 118 122 57 TC PI MBH kW 81.0 2.55 81.0 3.05 81.0 3.75 81.0 4.43 81.0 4.70 81.0 4.96 81.
EDUS391005-R1 Capacity Tables (Reference Data) RXYQ120PBYD Combi- Outdoor nation air temp. % 130 120 110 100 °FDB 23 30 40 50 54 58 62 66 70 72 75 79 83 87 91 93 95 99 103 106 110 115 118 122 23 30 40 50 54 58 62 66 70 72 75 79 83 87 91 93 95 99 103 106 110 115 118 122 23 30 40 50 54 58 62 66 70 72 75 79 83 87 91 93 95 99 103 106 110 115 118 122 23 30 40 50 54 58 62 66 70 72 75 79 83 87 91 93 95 99 103 106 110 115 118 122 57 TC PI MBH kW 101 3.52 101 3.64 101 3.81 101 4.00 101 4.08 101 4.17 101 4.
Capacity Tables (Reference Data) EDUS391005-R1 RXYQ144PBYD Combi- Outdoor nation air temp. % 130 120 110 100 °FDB 23 30 40 50 54 58 62 66 70 72 75 79 83 87 91 93 95 99 103 106 110 115 118 122 23 30 40 50 54 58 62 66 70 72 75 79 83 87 91 93 95 99 103 106 110 115 118 122 23 30 40 50 54 58 62 66 70 72 75 79 83 87 91 93 95 99 103 106 110 115 118 122 23 30 40 50 54 58 62 66 70 72 75 79 83 87 91 93 95 99 103 106 110 115 118 122 57 TC PI MBH kW 121 3.59 121 3.70 121 3.88 121 4.07 121 4.15 121 4.24 121 4.
Capacity Tables (Reference Data) 8.2 EDUS391005-R1 Heating Capacity (RXYQ-PBYD) RXYQ72PBYD Combination Outdoor air temp. % °FDB °FWB -3.64 -4.0 -1.84 -2.2 5.5 5.0 9.5 8.5 13.0 12.0 15.0 14.0 17.0 15.5 19.0 18.0 22.0 20.0 26.0 24.0 30.0 28.0 35.0 32.0 39.0 36.0 44.0 40.0 47.0 43.0 51.0 47.0 54.0 50.0 57.0 53.0 60.0 56.0 -3.64 -4.0 -1.84 -2.2 5.5 5.0 9.5 8.5 13.0 12.0 15.0 14.0 17.0 15.5 19.0 18.0 22.0 20.0 26.0 24.0 30.0 28.0 35.0 32.0 39.0 36.0 44.0 40.0 47.0 43.0 51.0 47.0 54.0 50.0 57.0 53.0 60.
EDUS391005-R1 Capacity Tables (Reference Data) RXYQ96PBYD Combination Outdoor air temp. % °FDB °FWB -3.64 -4.0 -1.84 -2.2 5.5 5.0 9.5 8.5 13.0 12.0 15.0 14.0 17.0 15.5 19.0 18.0 22.0 20.0 26.0 24.0 30.0 28.0 35.0 32.0 39.0 36.0 44.0 40.0 47.0 43.0 51.0 47.0 54.0 50.0 57.0 53.0 60.0 56.0 -3.64 -4.0 -1.84 -2.2 5.5 5.0 9.5 8.5 13.0 12.0 15.0 14.0 17.0 15.5 19.0 18.0 22.0 20.0 26.0 24.0 30.0 28.0 35.0 32.0 39.0 36.0 44.0 40.0 47.0 43.0 51.0 47.0 54.0 50.0 57.0 53.0 60.0 56.0 -3.64 -4.0 -1.84 -2.2 5.5 5.
Capacity Tables (Reference Data) EDUS391005-R1 RXYQ120PBYD Combination Outdoor air temp. % °FDB °FWB -3.64 -4.0 -1.84 -2.2 5.5 5.0 9.5 8.5 13.0 12.0 15.0 14.0 17.0 15.5 19.0 18.0 22.0 20.0 26.0 24.0 30.0 28.0 35.0 32.0 39.0 36.0 44.0 40.0 47.0 43.0 51.0 47.0 54.0 50.0 57.0 53.0 60.0 56.0 -3.64 -4.0 -1.84 -2.2 5.5 5.0 9.5 8.5 13.0 12.0 15.0 14.0 17.0 15.5 19.0 18.0 22.0 20.0 26.0 24.0 30.0 28.0 35.0 32.0 39.0 36.0 44.0 40.0 47.0 43.0 51.0 47.0 54.0 50.0 57.0 53.0 60.0 56.0 -3.64 -4.0 -1.84 -2.2 5.5 5.
EDUS391005-R1 Capacity Tables (Reference Data) RXYQ144PBYD Combination Outdoor air temp. % °FDB °FWB -3.64 -4.0 -1.84 -2.2 5.5 5.0 9.5 8.5 13.0 12.0 15.0 14.0 17.0 15.5 19.0 18.0 22.0 20.0 26.0 24.0 30.0 28.0 35.0 32.0 39.0 36.0 44.0 40.0 47.0 43.0 51.0 47.0 54.0 50.0 57.0 53.0 60.0 56.0 -3.64 -4.0 -1.84 -2.2 5.5 5.0 9.5 8.5 13.0 12.0 15.0 14.0 17.0 15.5 19.0 18.0 22.0 20.0 26.0 24.0 30.0 28.0 35.0 32.0 39.0 36.0 44.0 40.0 47.0 43.0 51.0 47.0 54.0 50.0 57.0 53.0 60.0 56.0 -3.64 -4.0 -1.84 -2.2 5.5 5.
REFNET Pipe System EDUS391004-N 4. REFNET Pipe System 4.
REFNET Pipe System 4.3 EDUS391004-N Outdoor Unit Multi Connection Piping Kit RXYQ144~240PBYD (460V) RXYQ168~240PBTJ (208/230V) BHFP22P100U GAS-SIDE REDUCER (3) (φ 1) GAS-SIDE JOINT + GAS-SIDE REDUCER (1) to Outdoor Unit A 1-9/16 I. D. φ 3/4 I. D. φ 7/8 I. D. φ 1 I. D. φ 1-1/8 Gas-Side Reducer 9-7/16 9-1/16 7-7/8 6-7/16 5-1/16 to Outdoor Unit B I. D. φ 3/4 I. D. φ 7/8 I. D. φ 1 I. D. φ 1-1/8 I. D. φ 1-1/8 I. D. φ 1 I. D. φ 7/8 φ I. D.
EDUS391004-N REFNET Pipe System 1P218719 Installation of Outdoor Units 105 23
REFNET Pipe System EDUS391004-N 1P218720 24 106 Installation of Outdoor Units
EDUS391004-N REFNET Pipe System 1P218720 Installation of Outdoor Units 107 25
Daikin Applied Georgia 1765 West Oak Parkway, Ste. 500 Marietta, GA 30062 Michael M Eckert, LEED AP; Sales Engineer Cell: 678.372.5034 Michael.eckert@daikinapplied.
Submittal Data: DMS502B71 BACnet® Interface Job Name: GSU Humanties - Law Building Purchaser: Gainesville Mechanical Engineer: Stevens & WIlkinson Submitted To: Submitted By: Unit Designation: Schedule #: Location: Atlanta, GA For: Reference Date: 12.23.13 Model No.: Approval Construction FEATURES / BENEFITS x Integrate Daikin VRV, SkyAir and Duct-Free Split Systems with third party building automation systems supporting the BACnet protocol.
Submittal Data: DMS502B71 BACnet® Interface Daikin air conditioner monitoring and control points accessible through the DMS502B71 Check the appropriate box indicating the required integrated points for this project. Operation, configuration, and monitoring points Monitoring points Function Description Start / stop status Monitors the start / stop status of the air conditioner.
Submittal Data Sheet BRC1E72 - New Navigation Controller GSU Humanities - Law Building Atlanta, GA Stevens & Wilkinson Gainesville Mechanical ! " 12.23.