Service manual

ESIE03–01 Specifications
Part 1 – System Outline 1–61
3
1
4
5
3.11 FDYMP
Technical
specifications
The table below contains the technical specifications.
Electrical
specifications
The table below contains the electrical specifications.
Specification FDYMP71L7V1 FDYMP100L7V1 FDYMP125L7V1
Heat exchanger Length 0.770 mm 1.170 mm
Rows x stages x fin pitch 3 x 14 x 1.75 mm
No. of passes 7 13
Face area 0.226 m² 0.344 m²
Tube type HI-XA Ø7
Fin type Fin Rhombus type
Empty tube hole 0
No.of fans 2 3
Fan Nominal air flow (cooling) H: 19 m³/min
L: 14 m³/min
H: 27 m³/min
L: 20 m³/min
H: 35 m³/min
L: 24 m³/min
Nominal air flow (heating) H: 19 m³/min
L: 14 m³/min
H: 27 m³/min
L: 20 m³/min
H: 35 m³/min
L: 24 m³/min
Fan motor model
Fan speed 3 steps
Fan type Sirocco fan
Refrigerant circuit Type R407C
Safety and functional devices See page 1–63 and 3–18
Air filter Resin net
Insulation Heat Both liquid and gas pipes
Weight 38.1 kg 48.6 kg
Specification FDYMP71L7V1 FDYMP100L7V1 FDYMP125L7V1
Unit Phase 1~
Voltage 230 V
Frequency 50 Hz
Fan motor Phase 1~
Voltage 230 V
Power consumption 150 W 195 W 415 W
No. of motors x output 1 x 130 W 1 x 155 W 1 X 225 W