Service manual

Specifications ESIE03–01
1–48 Part 1 – System Outline
3
1
1
4
5
3.2 RP71
Technical
specifications
The table below contains the technical specifications.
Electrical
specifications
The table below contains the electrical specifications.
Specification RP71L7V1 RP71L7W1
Compressor
Model x No. JT90FA-V1N x 1 JT90FA-YE x 1
Type Hermetically sealed scroll type
Refrigerant oil type DAPHNE FVC68D
Speed rpm
Oil charge 1200 cc
Outdoor
Heat exchanger
Length 859 mm
Rows x stages x fin pitch 2 x 34 x 2.0 mm
No of passes 6
Face area 0.634 m²
Tube type HI-XSS Cooling tube
Fin type Non sym. waffle louvre
Empty tubeplate hole 0
No of fans 1
Fan
Nominal air flow (230V) cooling 48 m³/min
Fan motor model P47L11S
Fan speed 3 steps
Refrigerant circuit
Type R407C
Charge 2.8 kg
Safety and functional devices See page 1–63 and 3–19
Heat insulation Both liquid and gas pipes
Weight 79 kg 78 kg
Specification RP71L7V1 RP71L7W1
Unit Phase 1~ 3N~
Voltage 230 V 400 V
Frequency 50 Hz
No. of wire connections 3 wires for power supply
(including earth wire)
5 wires for power supply
(including earth wire)
4 wires for connection with indoor (including earth wire
Power supply intake Outdoor unit only
Compressor Phase 1~ 3~
Voltage 230 V 400 V
Starting method Direct
No. x motor output 1 x 2200 W
Fan motor Phase 1~
Voltage 230 V
No. of motors x output 1 x 65W