Service manual
ESIE03–01 Test Run and Operation Data
Part 4 – Commissioning and Test Run 4–35
3
4
5
1
Correlation of
Air- Conditioner's
Operation Status
and Pressure /
Running Current
What happens in comparison to normal values is summarized in the table below.
(Measured from 15 ~ 20 minutes or more after operation starts.)
When Cooling
When Heating
Note *1. Water in the refrigerant freezes inside the capillary tube or expansion valve, and is basically the
same phenomenon as pump down.
*2. Dirt in the refrigerant clogs filters inside the piping, and is basically the same phenomenon as pump
down.
*3. Pressure differential between high and low pressure becomes slight.
Air-Conditioner Status Low Pressure High Pressure Running Current
Air Filter Fouling Lower Lower Lower
Short Circuit of Indoor Unit Inlet/
Outlet Air
Lower Lower Lower
Outdoor Unit Fin Fouling Higher Higher Higher
Short Circuit of Outdoor Unit
Inlet/Outlet Air
Higher Higher Higher
Air Mixed in Refrigerant Higher Higher Higher
Water Mixed in Refrigerant *1 Lower Lower Lower
Dirt Mixed in Refrigerant *2 Lower Lower Lower
Lack of Refrigerant (Gas) Lower Lower Lower
Unsatisfactory Compression *3 Higher Lower Lower
Air-Conditioner Status Low Pressure High Pressure Running Current
Air Filter Fouling Higher Higher Higher
Short Circuit of Indoor Unit Inlet/
Outlet Air
Higher Higher Higher
Outdoor Unit Fin Fouling Lower Lower Lower
Short Circuit of Outdoor Unit
Inlet/Outlet Air
Lower Lower Lower
Air Mixed in Refrigerant Higher Higher Higher
Water Mixed in Refrigerant *1 Lower Lower Lower
Dirt Mixed in Refrigerant *2 Lower Lower Lower
Lack of Refrigerant (Gas) Lower Lower Lower
Unsatisfactory Compression *3 Higher Lower Lower