3.1 General Operation Data
During cooling
mode and dry keep
The operating conditions must be as follows:
The operation values are guidelines in the operation range:
P LP: 3.0~6.5 barg (low pressure)
P HP: 12.0~28.0 barg (high pressure)
P Td: 60~95°C (discharge pipe temperature compressor)
P Ts: -2~15°C (suction pipe temperature compressor)
P Ti: 8~16°C (indoor temperature difference air return – air outlet ).
During heating
mode
The operating conditions must be as follows:
The operation values are guidelines in the operation range:
P LP: 1.8~6.4 barg (low pressure)
P HP: 13.0~28.0 barg (high pressure)
P Td: 55~95°C (discharge pipe temperature compressor)
P Ts: -15~10°C (suction pipe temperature compressor)
P Ti: 12~32°C (indoor temperature difference air return – air outlet ).
Items Operating modes If the operation is out this range...
Outdoor temp.
P c/o: -15 to +46°CDB
P h/p: -5 to +46°CDB
P A safety device may stop the operation.
P Condensation may occur on the indoor unit and
start dripping.
Indoor temp. +14 to +28°CWB
Indoor humidity 80%
Items Operating modes If the operation is out this range...
Outdoor temp. -10 to +15.5°CWB A safety device may stop the operation.
Indoor temp. +15 to +27°CDB