Service manual

ESIE03–01 Field settings
Part 4 – Commissioning and Test Run 4–31
3
4
5
1
DS2-4:
Method and
illustration
The capacity will be increased when the dip switch DS2-4, mounted on the outdoor PCB, is set to ON
.
Detail dip switch setting:
DS2-4:
Capacity result at
low temperature:
The capacity increases when outdoor temperature drops below 21°C as indicated on table below:
*This is a relative comparisson to indicate an increase of 50 to 100% capacity with the dipswitch ON.
Note See page 2–29 “Freeze up conditions” for detailed information.
DS2-4: Caution
P Finally the capacity result will depend on the total condition of the installation site. This is the
responsibility of the customer.
P There is additional limitation for the relative humidity when operating this switch. Finally it will
depend on the total condition of the installation site and is responsibility of the customer.
P Evaluation is necessary for each installation site by a proffesional responsible installer.
P Only use the switch for capacity increase in the area indicated on the graph of page 4.
P Do not set the switch in combination with the option EKRPER, this is only for use of Daikin indoor
units.
OFF (Factory setting) ON
DS2
ON
OFF
1 2 3 4
DS2
ON
OFF
1 2 3 4
Dip switch OFF (Factory setting) Dip switch ON
Capacity low temperature 100%* 150~200%
Reason for limitation:
When operating with switch ON, there will be a change of freeze protection control see table on
next page. By this there will be some risk of:
P Ice building up at indoor heat exchanger.
P Water blown off from the unit into the room