Field settings ESIE03–01
4–30 Part 4 – Commissioning and Test Run
3
1
4
5
2.15 DIP switch DS2
DS2-3:
Freeze 1
The table below describes the DIP switch.
DS2-4:
Freeze 2
The table below describes the DIP switch.
Setting Illustration Function
Factory setting OFF Enables the “intelligent” control function.
See page 2–29.
Field setting ON Disables the “intelligent” control function.
Freeze-up start/stop decided by indoor unit.
(Unit will restart when evaporator temperature
reached 70°C for 10 minutes.)
To be used in combination with EKRPER only!
1234
1234
Setting Illustration Function
Factory setting OFF Normal operation.
Field setting ON Countermeasure for low humidity applications.
1234