Service manual
ESIE03–01 Field settings
Part 4 – Commissioning and Test Run 4–27
3
4
5
1
BS The table below contains the BS field setting.
Pump down Pump down is preferably carried out with the indoor unit set to “fan only” in order to avoid compressor
restart with closed stop valves after finishing the previous pump down operation (close stop valves,
turn OFF the power supply).
If accidentally, the power was switched back ON, the unit will automatically restart with closed stop
valves, which may result in a possible compressor breakdown.
BS Label on PCB Function Applicable units Details
BS1 Pump down / forced
defrost
Cooling/fan only: Pump down (see further
in this section)
Heating: Forced defrosting
P RP71-125L
P RYP71-125L
—