Service manual

Field settings ESIE03–01
4–16 Part 4 – Commissioning and Test Run
3
1
4
5
2.7 Setting the Filter Counter
Mode No. 10 or 20
First code No. 0
When the filter counter indication time is set to ON, set the second code No., according to the table
below
Fan speed OFF
when
thermostat OFF
When the cool/heat thermostat is OFF, you can stop the indoor unit fan by switching the setting to
“Fan OFF”. This setting is used as a countermeasure against odour, for example for barber shops and
restaurants.
Fan speed
changeover when
thermostat OFF
You can switch the fan speed to the set fan speed when the heating thermostat is OFF. This setting is
called “Set Fan Speed”.
Air flow direction
setting
Set the air flow direction of the indoor units as given in the table below. This setting is needed when
the optional air outlet blocking pad has been installed. The “Second code No” is factory set to “01”.
Unit Mode No. First code No. Second code No. Contamination
01 02
light heavy
FHYCP
10 or 20 0
±2500 hrs ±1250 hrs
FHYKP ±2500 hrs ±1250 hrs
FHYP ±2500 hrs ±1250 hrs
FUYP ±2500 hrs ±1250 hrs
FAYP~L ±200 hrs ±100 hrs
FATP~B ±200 hrs ±100 hrs
FHYBP ±2500 hrs ±1250 hrs
FDYMP ±2500 hrs ±1250 hrs
FDYP ±2500 hrs ±1250 hrs
Mode No. First code No. Second code No. Setting
11 or 21 2
01
02 Fan OFF
Mode No. First code No. Second code No. Setting
12 or 22 3
01 LL fan speed
02 Set fan speed
Mode No First code No Second code No Setting
13 or 23 1
01 F: four-direction air flow
02 T: three-direction air flow
03 W: two direction air flow