Service manual

ESIE03–01 Error Codes: System Malfunctions
Part 3 – Troubleshooting 3–63
3
3
4
5
1
4.3 Reverse Phase (U1)
Error code U1
This error code is only for 3-phase equipment.
Error generation The error is generated when the difference between phase L1 and L3 is not 240°. The illustration below
shows the 3-phase network.
Causes The possible causes are:
P Malfunctioning power supply wiring connection
P Broken or disconnected power supply wiring
P Malfunctioning outdoor unit PCB
12090 180
L1 L2 L3
240
240˚
270 360
L1
L3 L
2
240˚
120˚