Service manual
ESIE03–01 Error Codes: Outdoor Units
Part 3 – Troubleshooting 3–55
3
3
4
5
1
3.10 Malfunctioning Outdoor Thermistor System (H9)
Error code H9
Error generation The error is generated when the thermistor resistance is out of its range (60ø to 600kø).
Causes The possible causes are:
P Malfunctioning outdoor thermistor
P Malfunctioning outdoor thermistor connector connection
P Malfunctioning outdoor unit PCB.
Troubleshooting To troubleshoot, proceed as follows:
Checking the
thermistor
resistance
See page 3–79.
Is
it connected
properly?
Correct the
connection.
Check the thermistor resistance.
Refer to:
checking the
thermistor resistance
.
Is it normal?
Replace the
termistor.
Replace the
outdoor unit PCB
No
Yes
No
Yes
Check the unit
type.
Check the connector
connection of the outdoor
temperature sensor (R1T) on
X4A on the outdoor unit PCB.