Error Codes: Outdoor Units ESIE03–01
3–52 Part 3 – Troubleshooting
3
1
3
4
5
3.8 Malfunctioning in Discharge Pipe Temperature (F3)
Error code F3
Error generation The error is generated when:
P Discharge pipe temperature becomes abnormally high
P Discharge pipe temperature rises suddenly
P Discharge pipe thermistor is not in its holder.
Causes The possible causes are:
P Improper refrigerant amount
P Clogging refrigerant piping circuit
P Discharge temperature that is too low due to too much refrigerant or due to the discharge
thermistor being out of its holder
P Discharge temperature that is too high. The possible causes are:
P Electronic expansion valve coil is disconnected from valve body
Excessively
high discharge
temperature
Refrigeration
shortage
y
electrical fault coil
y
mechanical fault body
y
discharge thermistor
inaccuracy
insufficient suction
gas to
compressor
incorrect
operation of
expansion valve
caused by
caused by
caused by