Service manual

Error Codes: Outdoor Units ESIE03–01
3–50 Part 3 – Troubleshooting
3
1
3
4
5
3.7 Malfunctioning Electronic Expansion Valve (E9)
Error code E9
Error generation The error is generated when the following coil current condition is not met:
Open circuit < coil current < short circuit.
Resistance values The table below contains the reference resistance values.
Causes The possible causes are:
P Malfunctioning electronic expansion valve
P Broken or disconnected electronic expansion valve harness
P Malfunctioning electronic expansion valve connector connection
P Malfunctioning outdoor unit PCB
P Outside cause (electric noise...).
Grey Black Yellow Red Orange
Grey
—40-50 ø 40-50 ø 40-50 ø 40-50 ø
Black
40-50 ø 80-100 ø 80-100 ø 80-100 ø
Yellow
40-50 ø 80-100 ø 80-100 ø 80-100 ø
Red
40-50 ø 80-100 ø 80-100 ø 80-100 ø
Orange
40-50 ø 80-100 ø 80-100 ø 80-100 ø