Service manual
Error Codes: Outdoor Units ESIE03–01
3–46 Part 3 – Troubleshooting
3
1
3
4
5
3.5 Abnormal Low Pressure (Detected by the LPS) (E4)
Error code E4
Error generation The error is generated when the low-pressure switch is activated during compressor operation.
Causes The possible causes are:
P Malfunctioning refrigerant piping circuit
P Malfunctioning low-pressure switch
P Disconnected or broken low-pressure switch harness
P Malfunctioning low-pressure switch connector connection
P Malfunctioning outdoor unit PCB.
P Stop valve is left close
LPS settings The table below contains the preset LPS values.
Applicable units Abnormal Reset
R(Y)P71/100/125L < -0.3 bar > +0.5 bar